Poles Number: | 1P2P,3P |
---|---|
Type: | Mini |
Model Number: | DZ47-63 |
Brand Name: | Tengen |
Place of Origin: | China (Mainland) |
Place of Origin: | Zhejiang,China |
Product name: | 1P,2P,3P 400v DZ47-63(C20) mini circuit breaker mcb |
Pole: | 1P,2P,3P |
Model no.: | DZ47-63 |
Brand: | Tengen |
Current: | below 63A |
Frequency: | 50/60HZ |
Type of using: | household or other |
PCS/CTN: | 120pcs |
Packing: | Export box |
Quick Details
Specifications
1P,2P,3P 400v DZ47-63(C20) mini circuit breaker mcb
Application
1P,2P,3P 400v DZ47-63(C20) mini circuit breaker mcb has novel structure, reliable performance, high breaking capacity, pleasing outlook and small size. Its case and items are adopted by high fire-resistant and shockproof plastic, It mainly used in the building office, house and similar building for illuminating at Ac 50Hz or 60Hz, rated voltage below 400V,rated current below 63A,distribution circuit and equipment overload, short circuit protection. It can also be used for unfrequent switch over of the circuit under normal conditions. 1P,2P,3P 400v DZ47-63(C20) mcbconforms to be requirement of IEC 60898 &GB10963 standards.
Main Technical Parameter
Rated current of frame(Inm)A |
Pole |
Frequency HZ |
Rated Voltage(Ue) |
Rated current (In)A |
Rated service short circuit breaking capacity (Ics)A |
Rated ultimate short circuit breaking capacity(Ics)A |
Type of release |
||
Breaking circuit A |
Cos? |
Breaking circuit A |
Cos? |
||||||
63 |
1 |
50 |
230/400 |
6,10,16, 20,25,32 |
6000 |
0.7 |
|
|
C |
2 |
230/400 |
||||||||
3 |
400 |
||||||||
4 |
400 |
||||||||
1 |
230,230/ |
6,10,16 20,25,32 |
4000 |
0.8 |
|
|
D |
||
2 |
400 |
||||||||
3 |
230,400 |
||||||||
4 |
400 |
||||||||
63 |
1 |
400 |
50,63 |
4000 |
0.8 |
|
|
C,D |
|
2 |
230/400 |
||||||||
3 |
230/400 |
||||||||
4 |
400 |
Weight(g) |
1P |
2P |
3P |
4P |
102 |
208 |
308 |
408 |
Standard |
Rated current |
Pole |
Voltage |
Breaking capacity(A) |
BS3871-1 HCE898 |
Ito 40 |
1 |
240 |
4000 |
2,4,4 |
415 |
4000 |
||
IEC157-1 |
Into 40 |
1 |
220/240 |
6000 |
2,3,4 |
220/240 |
12000 |
||
2,3,4 |
380/415 |
6000 |
Overload current tripping characteristic
Testing |
Rated |
Limited time |
Pre-engage result |
Start state |
Note |
1.13Ih |
all |
t=1h |
non-trip |
cold state |
|
1.45Ih |
all |
T<1h |
trip |
cold state |
The current rise steadily to a fixed value within 5s |
2.55Ih |
In=32A |
1s<60s<div> |
trip |
cold state |
|
2.55Ih |
In>32A |
1s<120s |
trip |
cold state |
|
5In(C) |
all |
<div> |
non-trip |
cold state |
Open the supplementary switch connect the power |
10Ln(C) |
all |
t=0.1s |
trip |
cold state |
Open the supplementary switch connect the power |
10In(D) |
all |
t<0.1s |
non-trip |
cold state |
Open the supplementary switch connect the power |
50In(D) |
all |
T=0.1s |
trip |
cold state |
Open the supplementary switch connect the power |
Product Photo