Product Main

Quick Details

Model Number: FST-CT220
Brand Name: FORESIGHT
Place of Origin: China (Mainland)
String voltage measurement range: 0-285v
Discharge voltage range: 180V-280V
Discharge current: 1-100Amp
voltage measurement resolution: 0.01v
current measurement resolution: 0.1Amp

Specifications

General:

220V Battery Load Bank is specifically designed for the maintenance of the lead-acid battery discharge in the electricity sector. It is a new high-tech intelligent product that provides safe, reliable and convenient constant testing equipment for the DC system

Product Type:

Different discharge current range

String Voltage

220VDC

Discharge current Range

30A/60A/100A/150A200A

All above listed items are standard one. The voltage and currency can be customized according to client's certain demand. When you place order please indicate the voltage, currency, model and function as well as if you need single section supervision by wire or wireless.

Main Functions and Features:

1, Used to discharge to battery string removed from the system

2,

3, 4 adjustable stop points and multiple alarm designs to control the discharge process intelligently

4, 7inch LCD touch screen for easy operation and showing various parameters real time

5, Support RS232 real time monitoring by PC or SD Card download data after discharge

6, PC software for capacity evaluation and report generation

7, Optional wireless modules for 1.2V/2V/6V/12V cells voltage real-time measuring

1, On-line monitoring setting:
battery load unit 220VDC 1100Amp

Online monitoring for battery string: when the battery string is under the state of online discharge, uniform charge and floating charge, perform real-time online monitoring for all cells. The monitoring includes string voltage, cell voltage, discharge current, monitoring time of battery string, charge/discharge capacity of battery string and etc.

2. Discharge Setting

battery load unit 220VDC 1100Amp

Perform discharge of constant current taking advantage of intellectualized dummy load after the battery string is removed from system, set up the parameters of " discharge current" , " discharge time " , " discharge capacity" , " final protective voltage of whole pack" and" final protective voltage of cell" , and the tester could carry out discharge function automatically, display discharge current, battery discharged capacity, the whole pack voltage, cell voltage,Discharge time and etc at real time;


Features

Specifications

Model

  220/30

  220/60

  220/100

  220/150A

String Voltage measurement range

0285V

String Voltage Resolution

0.01V

Voltage measurement accuracy

0.5%

Cell Voltage Resolution

0.01V

 Discharge current Range

130A

160A

1100A

1150A

Discharge Voltage of Constance current and constant power

180280V

Resolutions

0.1A

Current measurement resolutions

1%

Power Supply

AC 100V- 220V±15%

50Hz/60Hz

Cooling mode

Air Cooling

Communication Mode

USB Communication port and SD Card storage

Display

7inch Touch screen

High-Voltage insulation test

Input-The enclosure: 2200Vdc 1min

Input-Output: 2200Vdc 1min

Output- The enclosure: 700Vdc 1min

Safety standard

EN610950

Work Temperature

-550

Storage Temperature

-4070

Humidity

Relative humidity 090%(40±2)

Noise

<60dB

Dimensions

40x225x300mm

480x225x410mm

600x250x410mm

600x225×x630mm

Weight

<10.5Kg

<13Kg

<18.5kgs

<25Kg