Product Main

Quick Details

Application: High Voltage
Material: Composite Polymer
Type: Insulator
Place of Origin: China (Mainland)

Specifications



Product details:

I. With the development and distribution lines insulated line transformation of the traditional design, since the insulation resistance line has inherent level of mine , bear a direct role thunder or lightning , lightning break, porcelain insulators , have already become a power bombed another face a new problem. FEG -type lightning Insulator is a new modular structure of combo products , take the first blockage dredge design , enhanced insulation and anti- contamination level, suitable for overhead line insulation support, but also has to prevent lightning overhead insulated wires break, blow up and reduction of porcelain insulators lightning trip protection. The principle is : When the voltage exceeds the insulation plug lightning over a certain value, the lightning rod and steel pillars arc flashover between the legs caused by discharge , short-circuit channel , successive frequency arc discharge gap will be combusted in order to protect the wire from burns. This product is used insulated wire is energized with a puncture Shihai function , without peel core insulating layer can avoid water and corrosion, installation and construction is extremely convenient and reliable. Since the post insulator and arc-proof fittings combined ( equipotential ) , without ring network power supply load side ( departure from the power supply side ) effects , more so simple and beautiful lines and greatly reduce the cost . The products are reliable , less investment , the effect is large , for the electricity sector to prevent lightning overhead insulated wire breakage provides a cost-effective way .


II. Specifications and Performance Parameters

Model Specification

Insulated conductor cross-section mm2

Lightning impulse withstand voltage ( peak ) KV

1min power frequency withstand voltage ( RMS ) KV

Dry Wet

Frequency arc current ( rms ) KA

Rated withstand bending load KN

Minimum nominal creepage distance mm

Remark

FPEG-12/5

50 /300

75

50 42

12.5

5

400

Piercing

FPEG-12C / 5

50 /300

75

50 42

12.5

5

400

Non Piercing


III. The structural characteristics
1) This product sub- piercing and non- piercing ( stripping insulation layer ) two kinds , the main by the insulation shield , clamp aluminum fittings , composite insulators, arc steel rod and the lower legs and other components.
2) Arc rod and clamp fittings assembled integrally connected , when lightning occurs, the arc between the legs of steel rods and caused flashover discharge , the formation of short -channel , successive frequency arc moves to the arc rods and steel feet between burning to protect the wires from burns. Stick arc bypass due to an optimal sheds and discharge gap , discharge and prevent burn better insulator sheds .
3) FEG-12/5 type with a puncture -type stab teeth structure , barbed teeth removable , skinning or skinning purposes optional . Barbed teeth using higher strength than aluminum and better electrical properties of the copper alloy , the surface through electrical ( infiltration ) with copper and aluminum plating process to prevent the oxidation , so that the line can be used as copper or aluminum . Piercing style without stripping wire insulation , avoiding core water and corrosion, installation and construction is extremely convenient, can greatly reduce the operator labor intensity .
4) Using composite materials than the PS-15 insulator porcelain insulators and other electrical insulating properties , and the creepage distance , improved anti- insulator contamination levels , which can meet the majority of users on the insulator contamination prevention requirements.
5) Insulation shield with silicone rubber material , has good insulation properties , anti-aging properties and flame retardance .
6) Has been taken into account to prevent birds from overhead wires causing a short circuit on the unique structure of harm .
7) Can tolerate about 5 times the frequency high- current arc burning .


IV. The installation method
1) Before installing the product , first check FPEG-12/5 pillars of high-voltage line lightning rod composite insulators and conductive arc voltage electrode assembly is securely connected into one , fastening nut of the high voltage electrode arc guiding rod and adjust to the desired position to ensure that the discharge gap against the direction and size.
2) Lightning Insulator clip trunking should be aligned parallel to the direction of conductors mounted on the cross arm , tighten the nut steel legs , equivalent to conventional insulators installation method, the arc rod toward the cross arm ( cross arm farthest distance ) away outside ; arc rod one direction , preferably towards the load side .
3) Puncture -type clamp way: according to wire section and weather temperature set torque wrench torque value : 26-32Nm, alternately using a torque wrench , tighten the two symmetrical pressure nuts. Inspection with the naked eye , you can see the basic thorn tooth root , and then tighten the nut prepared to prevent the pressure nut loose . ( Trillion
4) Non- puncture -type clamp way: insulated wire peel of an approximately 65-80mm embedded insulator clamp fittings on the compression nut with a wrench to tighten the seat clamp wire can be driven by briquetting ; insulation shield mounted on the clip external line fittings .


V. Conditions of Use
1, Ambient temperature : -40 °C ~ 50 °C
2, The altitude does not exceed : 1500m altitude
3, The maximum wind speed : 35m / s
4 , The earthquake intensity : 8


VI. The Reference Standard
GB/T20142-2006 nominal voltage greater than 1000V AC overhead line post composite insulator - Definitions, test methods and acceptance criteria
JB/T8177-1999 insulator layer of galvanized metal accessories General technical requirements.