Rated Voltage: | 35kV |
---|---|
Application: | High Voltage |
Material: | Composite Polymer |
Type: | Insulator |
Model Number: | FS-35/5, FS-35/10 |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
Withstand Voltage Polymeric Cross Arm Composite IAnsulator FS-10/2.5
Composite crossarm insulator can be used under 110kv overhead lines, especially for 6-35kv distribution lines. Crossarm insulators are used for small railway tunnel, urban narrow power distribution corridor, or urban power network reconstruction where streets are narrow. Silicone cross arm insulator can replace the function of crossarm.
Features:
1. Weather sheds of the composite crossarm insulator is designed for polluted conditions.
2. The thickness of the Interface of the core to housing is conformed to IEC;
3. It has consistent mechanical and electrical performance throughout entire service life;
4. It has competitive price and good quality.
Polymer cross-arm insulators specifications:
Type
Rated voltage
Rated bending
Center distance of line groove
Arcing distance
Creepage distance
Full wave lighting impulse
Wet power frequency
Line groove size
mounting size
Stable hole diameter
Center distance of
(kv)
failing load
and mounting hole
(mm)
withstand voltage
withstand voltage
mounting hole and stable hole
FS-10/2.5
10
2.5
400
315
460
165
65
11
18 17
6.5
40
FS-10/5
10
5
400
300
610
165
65
14
22 58
11
40
FS-35/5
35
5
620
520
1080
290
130
14
22 58
11
40
FS-110/5
110
5
1150
1030
3200
580
330
14
22 66
11
40
FS-220/5
220
5
2215
2050
6300
1000
395
14
22 82
11
35