Coil Number: | 6 |
---|---|
Coil Structure: | |
Phase: | Single |
Usage: | Current |
Model Number: | LB-132 |
Brand Name: | HYEE |
Place of Origin: | China (Mainland) |
Name: | 132kv 145kv single phase current transformer price |
Standard: | IEC/IEEE/GB |
Type: | Oil Immersed |
Internal insulation: | Oil |
External insulation: | Porcelain |
Color: | Brown/White |
Quick Details
Specifications
132kv 145kv single phase current transformer price
Purpose Standards Service condition LB-33GY(W1,W2,W3) less than 3500m |
Technical Data
Rared frequency | Hz | 50: 60 | |||
Rated voltage | kV | 66/69 | 110 | 132 | 220 |
Highest voltage for equipment | kV | 72.5 | 126 | 145 | 252 |
Power frequency withstand voltage on primary windings | kV | 160 | 230 | 275 | 460 |
Rated lightning impulse withstand voltage | kV | 350 | 550 | 650 | 1050 |
Flashover distance | mm | 700 | 1050 | 1300 | 2000 |
Creepage distance | mm | 1820: 2250 | 3150: 3910 | 3630: 4500 | 6300: 7820 |
Mechanical load | N | 2000 | 2000 | 2000 | 3000 |
Rated primary current | A | 50~1600 | 50~1600 | 50~1600 | 150~2000 |
Rated secondary current | A | 1:5 | |||
Accuracy class | 0.1: 0.2: 0.5: 0.2S: 0.5S: 5P: 10P: TPS: PX.... | ||||
Rated output (Recommended value) | FS | 1A: 10~15VA 5A: 30~50VA | |||
Instrument security factor | VA | 5: 10 | |||
Accuracy limit factor | ALF | 10, 15, 20, 25, 30 | |||
Short-time thermal current ( Maximum) |
KA | 50KA/3s (in series) |
Outline drawing