Product Main

Quick Details

Safety Standards: IEC
Breaking Capacity:
Usage: High Voltage
Model Number: DT-1501,DT-2701,DT-3602
Brand Name: OEM
Place of Origin: China (Mainland)
MATERIAL: POLYMER

Specifications

Specifications

33kv fuse
1,polymer base
2,Rated current: 100A, 200A
3,leakage distance: 440 to 790mm

 outdoor polymer drop out 33kv fuse cut outs     

 

Introduction

 

the Fuses are fitted in HV side of distribution transformer or o Distribution branches,acting as overload protection as well as the Function of opening and closing load current.the rated voltage cover from 12kV up to 36kV,rated current up to 200A.the fuse conforms to IEC282-2 standard.

outdoor polymer drop out 33kv fuse cut out
Parameters  

 
 outdoor polymer drop out 33kv fuse cut outs
Product Code DH-1501 DH -1502 DH -2701 DH -2702 DH -3601 DH -3602
Rated Voltage,kV 12/15 12/15 24/27 24/27 36 36
Rated Current,A 100 200 100 200 100 200
Rated Breaking current,A 10 12 10 12 10 12
BIL,kV 110 110 150 150 200 200
Power frequency withstand voltage (dry 1 min),kV 55 55 70 70 95 95
Leakage Distance,mm 440 440 600 600 790 790
Height H,mm 430 430 500 500 600 600
Tube length L,mm 310

310
380 380 480 480
Weight,kg 3.6 4.0 4.6 4.8 5.6 5.8
outdoor polymer drop out 33kv fuse cut out