Description:
the Interrupter adopts " one shut technology", ceramic shell, CuWC as the contact material;is characterized by high insulation, low stop-flow, strong blowout ability, long life, smallsize etc, and has advantages as easy to maintain, no explosion risk,pollution-free and lownoise etc. Contactors assembled by it are used to control and protect the electricity transmission and distribution system in electrical, mechanical, chemical, metallurgy, mining and railway department, especially in frequent operation fields.
Product Details Introduction
Rated working voltage: |
kV |
0.66 |
Rated working current: |
A |
211 |
Rated making current capacity: |
KA/times |
2.11/50 |
Rated breaking current capacity: |
KA/times |
1.7/50 |
Limiting breaking current capacity: |
KA/times |
3/3 |
Rated short-time withstand current /duration: |
KA/S |
1.7/10 |
Rated current on and off times: |
Times |
6×104 |
1 minute withstand voltage: |
KV |
4.5 |
Contact resistance under contact automatic |
Closing pressure: |
uΩ |
≤100 |
Mechanical Life: |
Times |
1×106 |
Contact automatic closing |
Force at atmospheric pressure: |
N |
43±15 |
Contact Max stroke: |
mm |
2 |
Counterforce at |
Contact rated stroke: |
N |
58±5 |
Contact erosion limit: |
mm |
1 |
Interrupter Max weight: |
Kg |
0.1 |
Storage duration: |
Year |
15 |
the specification required of the contactor structure |
Contact rated stroke: |
mm |
1 |
Contact Overtravel: |
mm |
1 |
Rated contact working pressure: |
N |
20 |
Average opening speed: |
m/s |
0.5~0.5 |
Average closing speed: |
m/s |
0.05~0.15 |
Contact closing bounce time: |
ms |
≤3 |
Three-phases synchronization: |
ms |
≤1.5
|