Safety Standards: | IEC |
---|---|
Breaking Capacity: | High |
Usage: | High Voltage |
Brand Name: | TID-TECH |
Material: | frp |
Place of Origin: | China (Mainland) |
Type: | Fuse Cutout |
Safety Standards: | ISO9001 |
Breaking Capacity: | 11 |
Usage: | POWER LINE |
Quick Details
Specifications
1.Using Environment Conditions:
1.1 Product Normal Using Conditions
1.1.1 Product normal temperature: -40℃~+40℃;
1.1.2 Altitude:1000M.
1.1.3 Max. Wind speed:35m/s.
1.1.4 Earthquake intensity: 8 degree.
1.2 Product is not suitable for following location:
1.2.1 Inflammation or explosive dangerous area.
1.2.2 Intensive shake or shock area.
1.2.3 Conducting electric,chemical gas as well as heavy pollution & salt fog area.
2.Mouting Method:
2.1 Mounting the fuse cutout on the bracket and fix it by bolt.
2.2 Setting the fuse cutout to the suitable position and fix it,making sure it is safe and stable.
2.3 Connecting the conduct wire with upper and lower joint clamp by boltt,it must be connected firmly.
3.Applied Standard:
IEC 62217 IEC60255 IEC60282
4.Technical Character:
Products Code Type Rated Voltage Rated Current Break Current Impulsed Voltage Power Frequency Voltage Creapage Distance
TP13101 CFC11/100 11kV 100A 10kA 110kV 40kV 230mm
TP13102 CFC11/200 11kV 200A 12kA 110kV 40kV 230mm
TP13201 CFC24/100 24kV 100A 10kA 125kV 45kV 330mm
TP13202 CFC24/200 24kV 200A 12kA 125kV 45kV 330mm
TP13301 CFC35/100 36kV 100A 6kA 170kV 70kV 660mm
TP13302 CFC35/200 36kV 200A 10kA 170kV 70kV 660mm
5. Material
Item Description of parts Material
1 Insulator parts Porcelain Insulator
2 Fuse tube parts epoxy resin with fiber glass winded vulcanized cotton arc extinction tube
3 Contacts parts Copper alloy with silver coating
4 Conductor parts Pure copper
5 No conductor metal parts Stainless Steel
6 Spring parts stainless-steel backup spring for sustained contact pressure
7 Thickness of Steel coating 80-120μm