Product Main

Quick Details

Brand Name: MULTIPOWER
color: grey
Theory: thermocouple calibration
Resolution: 0. 005
Size: 500*360*180mm

Specifications

General Description:GTMIII General Temperature Rise Testing Device

Temperature Rise testing is a key step in evaluating the operational reliability of new Grid components like transformers, switchgear, cables, generator, etc. Work Together with high current transformers,  GTM-III is used to measure  Switchgear  each  points  Temperature data up to 56.

GTM-III Is a simple temperature data logger, which can work with any high current transformers. They are separately other. with a mini printer, you can print the data after The test.

Features:

Temperature Benchmark preset in advance.

Advanced Filtering algorithm to filter off various interferences, such as power &double frequency, transient;

Support Thermocouple calibrating compared with the standard thermocouple.

All IEC thermocouples are supported, all temperature voltage tables are preloaded Already.

Controlled by micro computer and printed the temperature rise value of each testing point and the three environment temperature.

High Accuracy, error only 10uv

Sampling Interval time: 0-99 minutes for-set

Small, Simple, reliable and cheaper

 Main specifications:

Input:  220V, 50HZ

the  Max. Number of test measurement point 60, 4 Reserved(3-ambient temperature, 1-zero point, 56 available actually)

Voltage Range:0-19.9mv

Voltage Error: <0.5,
Temperature Resolution:0.005℃

Sampling Rate: 3pionts /second

Sampling Interval time: 0-99m for per-set

Ambient Temperature:-0℃~+50℃, RH(85%

Size:500*360*180mm, 12.5kg