| Type: | Ventilation |
|---|---|
| Brand Name: | DEC |
| Certification: | ISO9001:2015 |
| Size: | 52mm-610mm |
| color: | Silver black |
| Model Number: | DEC-XIAA/CXIA |
| Place of Origin: | China (Mainland) |
| Insulation: | Polyester/glass wool |
| Thickness: | 25mm/30mm/40mm/50mm |
| R-value: | 0.4/0.6/0.8/1.0 |
| Length: | 6m/7.5m/10m |
Quick Details
Specifications
DEC Flexible Duct designed for HVAC systems Is light weight, strong, fully flexible and compressible yet dimensionally Stable.
DEC Flexible Duct is made of double
Lamination of aluminum foil and polyster films permanently bonded to a copper
Spring tough steel wire helix. Thermal efficiency is provided by wrapping the
Exterior with a blanket of fiberglass wool insulation in various densities
& thicknesses(16kg/m3,24 kg/m3,32 kg/m3,25mm,30mm) for required thermal resistance or polyester
Insulation(25mm,30mm,R0.6,R1.0,R2.0). The outer jacket is made of double
Laminated aluminum foil with fiberglass yarn reinforcement, which acts as a
Vapour barrier surface as well.
DEC Flexible Duct can widely be used in all
Air Conditioning or Ventilating Systems including commercial & office
Buildings, hotels, hospitals and many other industrial and residential
Applications.
DEC Flexible Ducts apply for a variety of
Styles and constructions and provide the most economical solution to your air
Handling needs.
Installation
All the flexible duct shall be installed in A fully extruded position and bends made with adequate radius.
the maximum allowable sag, between any two Adjacent suspension points, should not exceed 50 mm per meter.
the distance between any two adjacent Suspension points may vary from 1.50 to 3.00 meter, depending upon the type of Flexible duct in use.
Flexible ducts mounted above suspended Ceiling should always be independently supported.
All bends should be made as large as Possible and should have a radius of not less than the diameter of the duct in Use. Double bends should be avoided, however if un-avoidable, ensure that each Radius is not less than R = 2 x D.
Ideally the hanging straps should supports the flexible duct with a minimum of half the circumference surface in contact, and without reducing the effective inside diameter of the duct. It is also Recommended that the minimum width of material to be used for the hanging Straps should be at least 25 mm.
Extra care should be taken when making Connection to fixed conventional ducts, and ensure that they do not become too Stressed. An additional support is recommended to overcome the potential Problem.
Light railing is a good alternative hanging
Support when using long length of flexible duct.