Product Main

Quick Details

Brand Name: leian
Rated Voltage: 48V
application: 4G base station
Material: Q235
name: DCDU

Specifications

  •  19 inches 1U standard rack installation;
  • 2 input and 10 outputs;
  • Good insulation for output terminals
  • Large discharge current and low residual voltage
  • Remote signal alarm connectors (dry contacts of remote signal alarm is closed at normal operation while open at fault condition). 
DCDU 48V DC power distribution unit

Product model

DCPD7A

Nominal operating voltage Uo

-48V

Max. Continuous operating voltage Uc

-75V

Frequency

0Hz

Protection modes

-48VRTN,-48VPE,RTNPE

Nominal discharge current In (8/20 us waveform)

-48VRTN:10kA;-48VPE:15kA;RTNPE:15kA

Max. Discharge current Imax (8/20 us waveform)

-48VRTN;15kA;-48VPE:15kA;RTNPE;15kA

Surge durability(8/20 us waveform)

-48VRTN:10kA;-48VPE:15kA;RTNPE:15kA

Rated load current IR

Input:160A(10 outputs, rated current 16A or Max. Current 25A for each output)

Limiting voltage

-48VRTN≤500V

Connection

Serial connection

Distribution capacity

One input and 10 outputs

Rated current of breaker

25A(for each output)

Local alarm indicator

None

Remote signal alarm connectors

Dry contacts 1 and 3 are closed at normal operation while open at fault.

Connector

Input: double crimping connectors

Output: Spring crimping connectors

Wire area

Input: 10~35mm 2

Output: 1~10mm2

Remote signal alarm:0.2~2mm2

Grounding connection

2 grounding terminals of Φ11mm on the front panel, M6 bolt for fixation

Dimensions

482.6mm179.5mm43.6mm