Ponovo PCT200i CT/PT Test System
PCT200 series CT/PT test set (CT Analyzer) is a current transformer test equipment
Specially designed for current transformer characteristic test and plus PT reference
Testing functions. There are two models, PCT200i and PCT200Ai. PCT200Ai has higher
Accuracy than PCT200i. Within builtin testing software based on Windows system in
Its local screen, PCT200 series are the test tool to finalize all the current transformer testing
without laptop control. 
and the reports can be managed and analyzed on PC and converted to multiresults reports in excel format.

PCT200 series CT and PT test set for current transformer and PT reference testing functions

Product Features

1.Can test M/P/TP type, bushing and GIS type CT

2.Ratio check up to 30000:1 and 45000:5
3.Knee point/Excitation Test check up to 45000V
4.More than 100,000 reports can be saved in its local storage, and support report software used
on the kit and on PC 
for managing and analyzing the reports
5.Standards: IEC600441/6, IEC618692, ANSI/IEEE C57.13, IS2705
6.Guess nameplate function
7.Results saved in Excel format
8.Report can be transferred to flash disk via USB port and view and print the report on a PC
9.Report could be customizable
10.Local sunlight readable LCD display, 8.4inch screen, within builtin Windows 7 system

11.Weight: 10kg/14kg
 


Various CT can be test
PCT200 series can test various CT, including transmission line CT, delta connection transformer, star connection
Transformer, CT with tapping, bushing type CT which requires large power output capacity, GIS type CT whose
Primary side length is long and requires large power output capacity, etc.

Following PT tests can be done automatically
Polarity
Excitation
Ratio
Burden



Main Specifications


Voltage output 0-120V
Current output 0~5Arms(15A peak)
Ratio check
Range 30,000:1 - 45,000:5
Accuracy 0.1%
Knee point check Max. 45,000V
Burden measurement
Range 0.05-200Ω
Accuracy ±0.1%±1mΩ Gur
Winding resistance test
Range 0.05-200Ω
Accuracy ±0.1%±1mΩ Gur
Phase displacement check
Accuracy 3 min Typ
Resolution 0.1 min
Other test functions
Accuracy limiting factor Yes
Instrument security factor Yes
Remanence flux Yes
Secondary time constant Yes
Unsaturated inductance Yes
Saturated inductance Yes
Symmetrical short circuit factor Yes
Accuracy limiting voltage Yes
Transient dimensioning factor Yes
Peak instantaneous error Yes
Composite error Yes
Dimensioins 470200245mm (WHL)
Weight 10kg/14kg




Current transformer test set PCT200iPCT200Ai