Product Main

Quick Details

Usage: Universal Testing Machine
Power: Electronic
Brand Name: PONOVO
Warranty: 12 months
weight: 23KG
Model Number: PW41i
Place of Origin: China (Mainland)
Certification: CE,ISO
COLOR: gray-white
Lead time: 2-4 WEEKS
Output: 3*40A,3*300V/4*300V

Specifications

PW41i Protection Relay Test Set Three-phase Relay Protection Tester


PW41i is a reliable protective relay test set with high current output (340A) and high
Voltage output (4300Vadvanced version or 3300V standard version). It is with built
in local system so that the testings could be done easily by the relay test set itself. the
PW41i advanced version also can be connected to external PC via PowerTest relay test
Software running to do testing as well. PW41i is a favorable and economical testing
Solution for commissioning work in distribution grid.


More Options for Different Testing Requirement


*PW41istandard version, 340A and 3300V, with local system testings only
*PW41iadvanced version, 340A and 4300V, with local system and support external PC control and support IEC61850 testings


Protection Relay Test Set PW41i
Features:

  1. 340A, 4300V/3300V
  2. 8 Binary inputs, 4 Binary outputs
  3. High current and power output, output 340A with maximum power up to 400VA/phase
  4. Auxiliary DC power supply 110V, ADJ(0300V, software controlled), 220V switchover
  5. the local software system is designed based on Windows system, which is easy and convenient for operation and upgrade. It supports using templates for various relay testings, for example, G59.
  6. Shortcut keys to simplify operation

Applications:
Relay test
.Distance protection relay
.Directional relay
.Current relay
.Voltage relay
.Frequency relay, etc.
Automatic device
.Synchronizer
.Autoreclosing
Power system simulation
.Transient, permanent state fault simulation
.Playback of COMTRADE format file
Calibration
0.5 Class energy meter
Disturbance recorder
Indicating meters, etc.

Main Specifications

Current

 

Range

3 x 40A

Power(typical)

3 x 400VA at 40A

Accuracy (typical)

0.16% reading + 0.04% range

Voltage

 

Range

3 x 0~300V

Power(typical)

3x 85VA at 300V

   

Accuracy (typical)

0.08% reading + 0.01% range

Frequency

 

Range

DC, 1 to1000Hz

Accuracy

0.002% at 50Hz

Phase angle

 

Range

0-360

Accuracy (typical)

0.2

Auxiliary DC supply

220V, 110V, ADJ(0-300V)

Binary input

 

Number

4

Type

POtential free

Binary output

1

Type

Potential free relay contacts,

Software controlled

Dimension

364*200*475mm

Weight

23kg