Products name: Grounding fault indicator RTU

Model: SNV309-EFI-IEC104/DNP3.0 RTU

Adapt for:

SNOVA,SNV-EFI, GroundingFault indicatorand EKL series short Grounding fault and short circuit indicator, integrating into SCADA, via 2G/4G network.

Grounding fault Indicator RTU SNVEFI IEC104 RTu

I. General introduce.

 SNOVA,Grounding fault indicator RTU, Version SNV309-EFI- IEC104/DNP3.0, it is professional used forSNOVA,SNV-EFI, GroundingFault indicatorand EKL series short Grounding fault & short circuit indicator, integrating into SCADA, via 2G/4G network. and achieve the grid smart management.

 

 It support both protocol of DNP3.0 and IEC104 at same time. User need not to do any changes on the device.  It only need to choose different communication port in the user SCADA system. It can integrate by two SCADA system at same time.

 

II. Guidance for integrate process. Hardware parts connection and installation:

Step 1:

Insert APN SIM card into SIM card slot(Note:FullSize SIM card).

Step 2: ConnectGPRSANTENAon the case terminal.

Step3: Insert the Battery terminal on the PCB.

Step4: Connect Solar power cable via the Solar power panel.

Step5: Connect the EFI between RTU via cables according wiring scheme.


 IEC104& DNP3.0 RTU Parameter setting:

 Using SNV308&SNV309 parameter setting APP via PC to set this parameter.

1. First connect RTU between computer via data cable.

2. Run the Parameter setting APP on PC.

3. Choose suitable port, and input correct parameter on setting APP interface as below.

3.1 Network parameter

APN:

User name:          (Tips: if the SIM card have no user name, then no filled)

Password:            (Tips: if the SIM card have no user name, then no filled)

 

3.2 DNP3.0 protocol parameter

 

Master link address: 1          

(note: it means SCADA server address, set as:Source in SCADA server)

Slave (Destination) link address:3    

(note: it means RTU address,set as:Destination  in SCADA server)

Port: 20000

Tips:  According DNP3.0 protocol define, the below setting is standard, normally, it is no need to change. If user SCADA system is really different, then Change it by professionals.

 

3.3 IEC104 protocol parameter

 

3.3.1  Msg Timeout. T1  default:  15s

3.3.2  Msg Timeout.T2   default: 10S

3.3.3  Msg Timeout. T3  Default: 30S

Remark:  

T1, T2, T3.  It use for the network state have a timeout value. It makes SCASA system between Terminal communication have a timeout buffer. If want to change, it need to accordingSCADASystem communication speed to adjust the T1,T2,T3 value big or small.  

Suggest, not to change it, otherwise professor is available to change it.

 

3.3.4ASDU Address   Default:3.

 

3.3.5Port: 2404

 

(More detail, please contact with the relate Engineer.)

 


III.Terminal RTUUpload data

  the SNV309-EFIRTU is supportedtoUpload with Max.12 set Grounding fault indicators.

the upload data related the connect number on the SNV309-EFI terminal No. (from 1#, 2#...12#).  through the SCADA, It can achieve the below main performances.

 

    1) When Grounding fault indicator detect a grounding fault, then it can upload the fault signal to SCADA.

2)through SCADA, Operator can operate to Remote reset the indicator, or Test the indicator

 SNV309-EFI, DNP3 Data Objects

Supported DNP3 data objects 

1. BInary input - with flags

Group:  1

VAriation:  2

Function code:

0x01 (READ)

Supported Qualifier:

0x00, 0x01, 0x06

DAta point quantity:

56

 

2. Analog input - single-precision, floating-point with flags

Group:  30

VAriation:  5

Function code:  

0x01 (READ)

Supported Qualifier:

0x00, 0x01, 0x06

DAta point quantity:

42

 

3. CLass 0 objects

Group:  60

VAriation:  1

Function code:  

0x01 (READ)

Supported Qualifier:  

0x06

BRief:  

Get all of the static data

 

4. Time and date

Group:  50

VAriation:  1

Function code:  

0x02 (WRITE)

Supported Qualifier:  

0x07

BRief:  

Set absolute time

 

5. Binary output - packed format

Group:  10

VAriation:  1

Function code:  

0x02 (WRITE)

Supported Qualifier:  

0x07

BRief:  

REset or Test EFI device

Annex.List of DNP3.0

BInary input point list (Signal)

Index

Name

EFI 1#,  Fault

EFI 2#, Fault

EFI 3#, Fault

EFI 4#, Fault

EFI 5#, Fault

EFI 6#, Fault

EFI 7#, Fault

EFI 8#, Fault

EFI 9#, Fault

EFI 10#, Fault

10 

EFI 11#, Fault

11 

EFI 12#,  Fault

 

Analog input point list (Measure)

Index

Name

Unit

TErminal battery voltage

V

Solar panel voltage

V

Terminal temperature

Mobile signal strength

dBm

 

BInary output point list

1. Reset EFI

Index

Name

800 

Reset all EFI, at same time

801 

Reset EFI 1#

802 

Reset EFI 2#

803 

Reset EFI 3#

804 

Reset EFI 4#

805 

Reset EFI 5#

806 

Reset EFI 6#

807 

Reset EFI 7#

808 

Reset EFI 8#

809 

Reset EFI 9#

810 

Reset EFI 10#

811 

Reset EFI 11#

812 

Reset EFI 12#

 

 

 

2. Test EFI

Index

Name

900 

TEst all EFI, at same time

901 

Test EFI 1#

902 

Test EFI 2#

903 

Test EFI 3#

904 

Test EFI 4#

905 

Test EFI 5#

906 

Test EFI 6#

907 

Test EFI 7#

908 

Test EFI 8#

909 

Test EFI 9#

910 

Test EFI 10#

911 

Test EFI 11#

912 

Test EFI 12#

 

 

 SNV309-EFI, IEC104 Data Objects

Annex.List of IEC104

1. Remote signal

ASDU type:

Type ID

Name

Abbreviation

1

Single-point information

M_SP_NA_1

 

List1:

IOA

Name

101

EFI #1Fault signal

102

EFI #2Fault signal

103

EFI #3Fault signal

104

EFI #4Fault signal

105

EFI #5Fault signal

106

EFI #6Fault signal

107

EFI #7Fault signal

108

EFI #8Fault signal

109

EFI #9Fault signal

110

EFI #10Fault signal

111

EFI #11Fault signal

112

EFI #12Fault signal

 

 

2. Remote Measurement

ASDU Type:

Type ID

Name

Abbreviation

13

Measured value, short floating point number

M_ME_NC_1

List2:

IOA

Name

201

RTU Battery voltage(V)

202

Solar Panel Voltage(V)

203

RTU inside temperature(℃)

204

GPRS signal intensity(dBm)

 

3. Remote control

ASDU type:

Type ID

Name

Abbreviation

45

Single command

C_SC_NA_1

 

List3:

IOA

Name

800

Reset allEFI, at same time

801

ResetEFI 1#

802

ResetEFI 2#

803

ResetEFI 3#

804

ResetEFI 4#

805

ResetEFI 5#

806

ResetEFI 6#

807

ResetEFI 7#

808

ResetEFI 8#

809

ResetEFI 9#

810

ResetEFI 10#

811

ResetEFI 11#

812

ResetEFI 12#

List4:

IOA

Name

900

Test allEFI ,at same time

901

Test  EFI 1#

902

Test  EFI 2#

903

Test  EFI 3#

904

Test  EFI 4#

905

Test  EFI 5#

906

Test  EFI 6#

907

Test  EFI 7#

908

Test  EFI 8#

909

Test  EFI 9#

910

Test  EFI 10#

911

Test  EFI 11#

912

Test  EFI 12#

 

4. SCADA Timing:

ASDU type:

Type ID

Name

Abbreviation

103

Clock synchronization command

C_CS_NA_1

IV.Attachment for RTU LED blinking define:

1)  the big GreenLED on Case outside

Normal running

Blinking type

1,RTU star running

Light on:150msLight off:150ms,

Blinking on: one times,Stop:2s.

Recycling..

2,Connected  with SCADA success

Light on:200msLight off:200ms,

Blinking: two times,Stop:2s,

Recycling...

None Normal state

Blinking type

1,SIM Problems:

None SIM card; Need input APN password. Etc.

Light on:100msLight off:150ms,

Blinking on: 3times,Stop:1s,

Recycling blinking..

2,Connect network failed:

   Can not register network or build link failed

Light on:100ms Light off:150ms,

Blinking:4,Stop:1s,

Recycling blinking..

3,MODEM Module wrong:

  Module welding failed, or Module bad.

Light on:100ms Light off:150ms,

Blinking: 5,Stop:1s,

Recycling blinking..

 

2)  LED on PCB in the case

PCB Position

Function

Description

D4

Blue color LED:
Indicating for GPRS module (A7600C1) working state

Normal light:It means searching network;

BlinkinG light, light on:200ms,Light off:200ms:

It means:net work registered, or data connect link build

Light off:It means:power off

D8

Yellow color LED:
Indicating for EFI fault signal

Normal state: Light off

Blinking 3times: it means RTU detect a fault signal from EFI

D7

Green color LED:
Indicating for GPRS communication state

Normal state: Light off

Blinking light: RTU upload or Receive signal between SCADA

D6

Red color LED:
Indicating for MCU state of RTU

When  MCU normal working, the LED keep blinking light.

D5

Indicating for power system of RTU

When the power system is normal, then it will be light on