Product Main

Quick Details

Model Number: DC-1008
Unit Type: Set
Package Size: 40cm x 35cm x 12cm (15.75in x 13.78in x 4.72in)
Package Weight: 6.32kg (13.93lb.)

Specifications

Product Features

 

  • 8,Class B Initiating Device Circuits (IDCs)

          All zones accept conventional detectors and any normally open contact device

  • Four Class B Notification Appliance Circuits (NACs)
  • One Form-A Alarm Relay
  • One Form-A Trouble Relay
  • One Form-A Supervisory Relay
  • 3.0 amps of system power
  • Max 20 conventional detectors in one zone.
  • Auto/Manual mode setting enable walk test.
  • Each Zone can be disabled,
  • Sound output can be disabled.
  • Manual active sound output enabled.
  • Able to report short and broken circuit of detection zones.
  • Designed with standby batteries and space provision for two sealed lead-acid batteries.
  • Testing and disable functions.
  • Can connect max 32 repeater panels by RS485 communication por
  • Specifications
  • AC Power

    90-270 VAC, 50 Hz, 2.3 amps

    Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

    Battery (lead acid only)

    Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

    Maximum Charger Capacity: 18 Amp Hour batter

    Sound Output Device Circuits

    General Alarm Zones 1 through 16

    Operation: All zones Class B

    Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

    Alarm Current: 15 mA threshold

    Short Circuit Current: 42 mA maximum

    Maximum Loop Resistance: 100 ohms

    End-of-Line Resistor: 4.7K, ½ watt

    Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

    Standby Current: 7.26 mA

    Three Relays Output

    Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

    Nonresettable 24 VDC Power

    Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

    Total DC current available from this output is up to 500 mA

    Recommended maximum Standby current is 150 mA

  • Circuits

     

    Input Circuits

    Sixteen input circuits provide configuration. Input circuits 1 through 16 may be used as standard fire alarm control panel zones. All sixteen Initiating Device Circuits accept normally-open contact devices and two-wire smoke detectors.

     

    Output Circuits

    •   24 Volt Resettable Power Output 1000 mA

    •   24 Volt Nonresettable Power Output 1000 mA

    •   24 Volt Battery Charger (up to 18 AH batteries)

    •   EIA-485 Port (interfaces to Annunciators, and Graphic Annunciators and Remote Relay Module)

     

    Sound (Notification Appliance )Circuits

    Four Notification Appliance Circuits.

     

    Relays

    Three dry relays for system alarm, system trouble and supervisory are provided standard. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive).

     

    EIA-485 Port

    EIA-485 compatible port supports up to 32 repeater panels.

     

    Battery Charger

    Battery Charger will charge up to 18 AH batteries.  The PANEL cabinet holds a maximum of 7 AH batteries. The external box is required to hold 18 AH batteries.  The charger is rated for 500 mA maximum current.