red 8 zones Fire Alarm Control Panel with 8Zones work with any 2wire  smoke detectors  fire alarm system

AC Power

90-270 VAC, 50 Hz, 2.3 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

Maximum Charger Capacity: 18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 8

Operation: All zones Class B

Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current: 15 mA threshold

Short Circuit Current: 42 mA maximum

Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 7.26 mA

Three Relays Output

Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA

8zone

Conventional Fire Alarm Control Panel with eight Zones

Key Specifications/Special Features
Eight Style B (Class B) Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
Alarm, Trouble and Supervisory, Form-C relays standard.
24-volt operation.
Each zone can be connected 25 detector devices 
output 2 groups sound and light
Can provide 12v voltage ,to connected anti-theft device for accommodating 
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
One-man walk-test programmable for silent or audible test.
Disable/Enable control per IDC.
Reverse polarity protection.
All zones accept conventional detectors and any normally open contact device
l Four Class B Notification Appliance Circuits (NACs)
l One Form-A Alarm Relay
l One Form-A Trouble Relay
l One Form-A Supervisory Relay
l 3.0 amps of system power
l Max 20 conventional detectors in one zone.
l Auto/Manual mode setting enable walk test.
l Each Zone can be disabled,
l Sound output can be disabled.
l Manual active sound output enabled.
l Able to report short and broken circuit of detection zones.
l Designed with standby batteries and space provision for two sealed lead-acid batteries
 

Package Size:420x480x180mm, 1 set/1 carton.  Gross Weight: 7Kg.