Certification: | ROHS,CE |
---|---|
Type: | Servo Motor |
AC Voltage: | 208-230 / 240 V |
Protect Feature: | Waterproof |
Efficiency: | IE 4 |
Model Number: | M7284A1004 |
Phase: | Single-phase |
Unit Type: | piece |
Package Size: | 20cm x 10cm x 8cm (7.87in x 3.94in x 3.15in) |
Package Weight: | 3.5kg (7.72lb.) |
Quick Details
Specifications
M7284A1004 17Nm Honeywell Damper Actuators Modutrol Motor For Burner New Original
APPLICATION
The Series 71, 72 and 76 Modutrol IV Motors are spring return and non-spring return motors used to control dampers and valves. The motors accept a current or voltage signal from an electronic controller to position a damper or valve at any point between open and closed.\
FEATURES
• Replaces M734H,J,; M744S,T,Y; and M745L,S,T,Y Motors.
• M7164, M7261, M7284, and M7294 are non-spring return motors; M7282, M7285, M7286 and M7685 are spring return motors.
• Integral spring return returns motor to normal position when power is interrupted.
• Integral junction box provides NEMA 3 weather protection.
• Motor and circuitry operate from 24 Vac. Models available with factory installed transformer, or a field added internal transformer.
• Quick-connect terminals are standard—screw terminal adapter is available.
• Adapter bracket for matching shaft height of older motors is available.
• Most motors have field adjustable stroke (90° to 160°).
•Die-cast aluminum housing.
• Integral auxiliary switches are available factory mounted, or can be field added.
• Nominal timing standard of 30 seconds (90° stroke), and 60 seconds (160° stroke). Other timings available.
• Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications.
• All models have dual shafts (slotted and tapped on both ends).
• All models have auxiliary switch cams.
• Fixed torque throughout the entire voltage range.
• Motors are designed for either normally open or normally closed valves and dampers.
• Models available with adjustable start (zero) and span.
• Models available with 4 to 20 mA input signal.
• Models available with 2 to 10 Vdc input signal.
Die-cast aluminum housing.
Specifications
· Application Type: Electric
· Fail Safe Mode: Non-Spring Return
· Control Signal: Modulating, 4-20 mA
· Motor Shaft: Dual ended Shaft
· Stroke: Adjustable; 90 to 160 degrees, symmetrical
· External Auxiliary Switches Available: Yes
· Frequency: 50 Hz, 60 Hz
· Power Consumption Driving (VA): 15 VA
· Shaft Dimensions (in.): .375 in
· Shaft Shape: Square
· Mounting: foot-mounted
· Dimensions: 6 7/16 in. high x 5 1/2 in. wide x 8 3/4 in. deep
· Temperature Range: -40 to 150F
· Deadweight Load on Shaft (Either End) (lb): 200 lbs
· Deadweight Load on Shaft (Combined on both shafts) (lb): 300 lbs
· Auxiliary Switch Ratings AFL - 120 Vac: 7.2A
· Auxiliary Switch Ratings AFL - 240 Vac: 3.6A
· Auxiliary Switch Ratings ALR- 120 Vac: 43.2A