Product Main

Quick Details

Model Number: LE3U 56MR6AD2DA
Motor Type: DC Motor
Brand Name: LOLLETTE
Input: 32
Output: 24
AD: 6
DA: 2
AD0-AD2: 0-10V
AD3-AD5: 0-20MA
Unit Type: piece
Package Size: 12cm x 15cm x 18cm (4.72in x 5.91in x 7.09in)
Package Weight: 0.7kg (1.54lb.)

Specifications

LE3U 56MR6AD2DA PLC programmable logic controller

Third party Programming Software Description: can be compatible with the programming software Developer7.8 GX or 8.52.8.5 .8.86 Version

32-point input, 24 relay outputs

X0-X5 high-speed input, can be accessed by three AB encoder, the default 12K, optional 100K
6 analog (3channel 0-10v, 3channel 0-20mA) 2 channel 0-10v analog output
Power-down to maintain, can be set free
DC 24V power supply

3-way AB input
Support for 16-bit encryption,
Supports three kinds of interrupts,
485 communication Support 4 kinds of communication protocols,
Support 1N, 2N, 3U of the instructions,
Power-down to maintain their own set range,
Program 8000 steps,
Download speed 38400,
Floating-point operations,
HMI,
Scan 3000 steps 1ms

Note :  since the international air does not allow the hair contains flammable and explosive goods, so the unity does not contain the battery delivery, thank you for understanding!

Input Power

DC24

Number of steps

8000 steps; 2 communication ports: 1 RS232 (DB9 serial port is communication port for the FX3u protocol 38400,7,E,1; 1 RS485 (485 selection)  communication protocol can be set D8120).

X input element

X0-X27 DC24 input,Low level,X0-5 is a high-speed count input port (the Default is 12K, 100KHZ optional)

Y output element

Y0-Y27 for optimal relay output,relay output current 5A.

4 continuation electric apparatus 1 common end, altogether 3 common ends

Analog input

6 analog input, 12 bit precision,  3 channel analog input 0-10V, 3 channel analog input 0-20MA; read analog RD3A instruction

Analog output

2 analog output, 12 bit precision, output voltage: 0-10V. output analog voltage with WR3A instruction

Intermediate relay

M0-M3071, power-down save range can be set M0-M1023, the default M500-M1023

Step point

S0-1023, power-down save range can be set S0-S1023, the default S500-S9999

100Ms timer

T0-T199 Accumulated power-down saving T184-T199

10Ms timer

T200-T249 Accumulated power-down saving T246-T249

1Ms timer

T250-T383, where T250-255 is the cumulative type

16-bit counter

C0-C199, power-down save C100-C199

32-bit counter

C200-C219, save the power-down C220-C234

32-bit high-speed counter

C235-255; C235-C240 for the single-phase counter, not multiplier; C241-240 for the single-phase calculator, 2 octave; C2470249 for the dual-phase counter, not multiplier; C250-252 for dual-phase counter, ; C253-C255 for the dual-phase counter, 4 octave

Register D

D0-D7999, power-down save the range can be set D0-7999

Indirect addressing pointer V, Z

V0-7, Z0-7

P The subroutine jump number

P0-63

I interrupt

X0-5 external interrupt, timer interrupt (1MS unit) counter interrupt

Special M components

M8000 run-time normally closed, M8002 power pulse, M8011 is 10Ms pulse,
M8012 is 100Ms pulse, M8013 is 1s pulse, M8014 is minute pulse

 

 

When setting the clock, the M8015 should be set to resume running M8015 reset. D8018 for the year, D8017 for the month, D8016 for the day, D8019 for the week, D8015 for the hour, D8014 for the minute, and D8013 for the second. You can use the clock data to read the instructions, TRD to read the clock data to the general register, or to use the clock to write instructions TWR, modify the clock, with this instruction do not set the M8015.
 

444