Model Number: | DVP06XA-H3 |
---|---|
Motor Type: | other |
Unit Type: | piece |
Package Size: | 30cm x 27cm x 23cm (11.81in x 10.63in x 9.06in) |
Package Weight: | 0.97kg (2.14lb.) |
Quick Details
Specifications
New Original Programmable Controller PLC 4 channel input 2 channel output 16-bit resolution Analog Module DVP06XA-H3
Features
Thank you for choosing the Delta DVP series PLC. Four channels on DVP06XA-H3 are able to receive analog input signals (voltages or currents), and convert them into 16-bit digital signals. Besides, two channels on DVP06XA-H3 can receive two pieces of 16-bit digital data from a CPU module, and convert the data into analog output signals (voltages or currents). Whether the analog input signals are voltage inputs or current inputs depends on the wiring. The voltage input range is ±10 V DC. (The resolution is 312.5 μV.) The current input range is ±20 mA. (The resolution is 0.625 μA). Whether the analog output signals are voltage outputs or current outputs also depends on the wiring. The voltage output range is ±10VDC. (The resolution is 312.5 μV.) The current output range is 0~20mA. (The resolution is 0.625 μA.)
Specification
Analog-to-digital conversion |
Voltage input |
Current input |
Supply voltage |
24VDC (20.4VDC~28.8VDC) (-15%~+20%) |
|
Number of channels |
4 channels |
|
Analog input range |
+ -10V |
+ - 20mA |
Coversion range |
+ -32,000 |
+ - 32,000 |
Resolution |
16 bits (1LSB=312.5uV) |
15 bits (1LSB=0.625uA) |
Input impedance |
Above 1M Ω |
250 Ω |
Overall accuracy |
25°C/77°F: + - 0.5% of the input within the range 0~55°C/32~131°F: + - 1% of the input within the range |
|
Response time |
1ms |
|
Isolation |
The internal circuit is isolated from the analog areas, and the channels are not isolated from one another. |
|
Average function |
Users can store the numbers of values averaged in CR#2~CR#5. Range: K1~K20. |
|
Self-diagnosis |
Upper/Lower limit detection/Channel |
|
Digital-to-analog conversion |
Voltage output |
Current output |
Number of channels |
2 channels |
|
Analog output range |
-10V~+10V |
0~20mA |
Data range |
-32,000~+32,000 |
0~32,000 |
Resolution |
16 bits (312.5uV) |
15 bits (0.625uA) |
Input impedance |
0.5 Ω or below |
|
Overall accuracy |
25°C/77°F: + - 0.5% of the input within the range 0~55°C/32~131°F: + - 1% of the input within the range |
|
Response time |
1ms |
|
Maximum output current |
20mA |
/ |
Permissible load impedance |
/ |
0 ~ 500 Ω |
Isolation |
The internal circuit is isolated from the analog areas, and the channels are not isolated from one another. |
|
Protection |
The voltage output is equipped with the short circuit protection. However, users must notice that a long-term short circuit will damage the internal circuit. The current output can be an open circuit. |
|
Connection with a DVP-PLC CPU |
The modules are numbered according to their distances from the CPU module. The numbers start from 0 to 7. Eight modules at most can be connected, and they do not occupy digital inputs/outputs. |
|
Rated maximum power consumption |
24VDC (20.4VDC~28.8VDC) (-15% ~ +20%); 4.5W An external power supply supplies the DC voltage. |
|
Operation/Storage |
Operation: 0°C~55°C (temperature); 50~95% (humidity); pollution degree 2 Storage: -25°C~ 70°C (temperature), 5~95% (humidity) |
|
Vibration/Shock resistance |
International standards IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) |