Product Main

Quick Details

Model Number: 1762-IR4
Motor Type: other
Unit Type: piece
Package Size: 1cm x 1cm x 1cm (0.39in x 0.39in x 0.39in)
Package Weight: 0.5kg (1.10lb.)

Specifications

1762-IR4 PLC New Original 4 input channels Specialty I/O Module

 

 1762 MicroLogix Expansion I/O

 

The 1762 MicroLogix expansion I/O modules are compatible with MicroLogix 1100, MicroLogix 1200, and MicroLogix 1400 controllers. If your application requires more I/O than the built-in I/O provided by the controller, add expansion I/O modules.
Install the expansion I/O modules to the right of the controller, either on a panel with two mounting screws or on a DIN rail. You can use digital and analog I/O modules in many combinations, up to the maximum supported by the controller. The current loading capacity of the controller’s built-in power supply may limit the actual number of I/O modules that can be connected to the controller.
Features

  • Integrated high-performance I/O bus
  • Software keying to prevent incorrect positioning within the system
  • Finger-safe terminal blocks for I/O wiring
  • Label to record I/O terminal designations
  • Network support includes EtherNet/IP, DeviceNet, and DH-485 (local only)
  • Digital, analog, and specialty I/O modules available

Specialty I/O Modules

Cat. No.

Inputs/Outputs

Accepted Inputs

Bus Current Load, Max.

Accuracy at 25 °C (77 °F)*

Resolution Across Full Range

Channel Update Time (Typical)

1762-IR4

4 input channels

• RTDs: Platinum (385 and 3916), Copper (426), Nickel (672 and 618), Nickel-Iron (518)
• Resistance Ranges: 0…3000 W

40 mA at 5V DC
50 mA at 24V DC

With autocalibration enabled
• RTD Inputs:
±0.2…±0.6 °C (±0.36…±1.08 °F), depending on RTD type
• Resistance Inputs:
±0.5…±1.5 Wdepending on resistance value

Input filter and configuration dependent

6…303 ms per enabled channel, depending on filter selection

1762-IT4

4 input channels plus a CJC sensor

• Thermocouple Types:
J, K, T, E, R, S, B, N, C
• Millivolt Input Ranges:
±50 mV and ±100 mV

40 mA at 5V DC
50 mA at 24V DC

±1.3 °C (±2.34 °F)

15 bits plus sign

7…303 ms per enabled channel +CJC update time

 Includes offset, gain, non-linearity, and repeatability error terms.
Refer to the MicroLogix 1200 RTD/Resistance Input Module User Manual, publication 1762-UM003, for more information. CJC update time is equal to the largest enabled channel\'s update time.