Product Main

Quick Details

Brand Name: Tanda
Sensor: smoke sensor
Size: L:190.87 x W:126.87 x H:91.96 mm / 440 gm
ITEM: Reflective Beam Detector
power: 20 V to 28 V DC
Model Number: TX7130
Place of Origin: China (Mainland)
Operating Voltage: 20 V to 28 V DC
Material / Colour: ABS / White
Current Parameters Standby: 23mA Commission:40uA Alarm:33mA
Beam Sensor Sensitivity: Level 1: 2.6 dB High Sensitivity Level 2: 3.4 Medium Sensitivity Level 3: 4.8 dB Low Sensitivity
Beam Path Angle: +-0.5 degree Directional
Reset Time: Less than 2 Second
Relay Capacity: Normally Open/ 2.0 A; 30 VDC Physical

Specifications

Skype firealarm87  /wechat 15220176087

Conventional Reflective Optical Beam Smoke detector Beam Detector Beam Alarm Sensor with Relay Output

Introduction

the Conventional Reflective Beam Detector has built in Laser beam pointing and Digital guide display for real
User friendly alignment method. the Laser beam pointing accurately point the exact location where to mount
Mirror and with additional digital guide display allows to monitor and guide on the actual light intensity between
the mirror and detector which cannot be seen by our naked eye making it more easy and convenient in
Alignment commissioning.
the beam detector has four adjustable operational range of between 8 to 20, 40, 70 and 100 meters beside
with three adjustable sensitivity setting ranges from 2.6dB to 4.8dB to meet the specific environmental
Requirement. the detector works on the principle of reflective infrared beam obscuration. Used in conjunction
with a reflectors, it will notify the fire alarm panel when the infrared beam is obscured by smoke. Secure and
Quick communication through the onboard processor enables the detector to make its own decision and drift
Compensation resulting in greater automation.
the detector is ideal for use high ceiling and wide areas such as warehouses, large storages, shopping malls,
Leisure centres, exhibition halls, hotel lobbies, printing houses, garment factories, museums and prisons, as well
as places where slight smoke particles or corrosive gas exist.


Feature and Benefits
1. Manufacture in compliance with EN54-12
2. Hassle free alignment, built with digital guide display and laser beam pointing
3. Employ single-ended design through reflective mirror.
4. Four ranges wide monitoring from 8-100 meters via encoder
5. Three users programing sensitivity adjustment
6. Built-in microprocessor
7. Self-diagnosis function can monitor for internal faults
8. Automatic compensation for factors weakening received signals, such as dust contamination, positional
Movement and ageing of the transmitter
9. Fire and Fault interfacing relays
10. Attractive and pleasing appearance
11. Real User friendly alignment method



Specifications

 Part Number 
Standard 
Compliance  EN54-12 
Fire Detection and Alarm Systems  BS 5839 Part 1:2002
Specification 
Operating Voltage  20 V to 28 V DC 
Current Parameters  Standby:23mA Commission:40A Alarm:33mA
Beam Sensor Sensitivity [via Encoder]  Level 1: 2.6 dB High Sensitivity
Level 2: 3.4 Medium Sensitivity
Level 3: 4.8 dB Low Sensitivity
Beam Pathway Length [via Encoder]  Span 1: 8 to 20 meters Short Path
Span 2: 20 to 40 meters Short Path
Span 3: 40 to 70 meters Normal Path
Span 4: 70 to 100 meters Long Path
Beam Path Angle  0.5 Directional
Alignment Guide  Laser Beam Pointer
Digital Display Guide  Nixie Tube 
LED Indicator Guide  Red: Fire; Yellow: Fault; Green: Alignment
Reset Time  Less than 2 Second
Relay Capacity [Fire & Fault]  Normally Open/ 2.0 A; 30 VDC
Physical 
Material / Colour  ABS / White 
Dimension / Weight  L:190.87 x W:126.87 x H:91.96 mm / 440 gm
Weight  0.130 Kg with base
Environmental 
Operating Temperature / Protection Rating  -10C to 55C / IP30 [IP66 glue seal]
Humidity  0 to 95% Relative Humidity, Non condensing


Adjustable Conventional Reflective Optical Beam Smoke detector Beam Alarm Sensor with Relay Output