Usage: | Personal |
---|---|
Brand Name: | king pigeon |
color: | bule |
GSM Frequency: | 850/900/1800/1900Mhz |
Power: | 9-36VDC |
Model Number: | M160T |
Place of Origin: | China (Mainland) |
Wiring: | I/O cable max. 14 AWG |
Dimensions: | 105 x 88 x 30 mm |
Weight: | Under 205 g |
Quick Details
Specifications
Modbus TCP Ethernet Remote IO Module (8DI+8DO+8AI+RJ45+RS485)
the M160T Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP, can be intergraded into SCADA, OPC server, and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.
the M160T Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet the industrial timely requirements.
the M160T Ethernet Remote I/O module provides 8 optical-isolated digital inputs, supports max. 10Mhz high speed pulse counter, 8 isolated 12bits analog inputs, supports 0~5V,0~10V,4~20mA,0~20mA analog signal, 8 digital outputs, supports 10Hz~300Khz high speed pulse output or relay outputs. All of the I/O with high sampling frequency and special filtering strategy to ensure it's reliable.
Features:
U Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;
U Power supply 12~36VDC with over voltage and phase-reversal protection;
U Embedded Web server for configuration and management;
U Support Web realtime monitoring and Web debugging;
U DO1 support PWM output;
U Integrated 10/100M adaptive Ethernet module, supports Modbus TCP protocol;
U 8 optical isolated digital input, supports max. 10Mhz high speed pulse counter;
U 8 digital output or relay output, supports 10Hz~300KHz high speed pulse output;
U 8 isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC;
U High sampling frequency and special filtering strategy to ensure reliability;
U 1 RS485 Serial port, supports Modbus RTU/ASCII Master, can extend I/O modules;
U Supports register mapping function and extend I/O inquiry strategy;
U Provides 1 channel 12~36VDC power source output for external device, saving wiring cost;
U LED instructions work status, with reset button to reset, easy on-site installation and commissioning;
U Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field;
U Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.
M160T Specifications
Ethernet Remote I/O Module Specifications | |
Digital Input | |
Sensor Type |
Wet Contact (NPN or PNP), Dry Contact |
I/O Mode |
DI or Event Counter |
Dry Contact |
on: short to GND=1 |
Wet Contact (DI to COM) |
on: 10 to 30 VDC=1 |
Counter Frequency |
Max. 10MHz(Only the 1st Channel can be used as high speed pulse counter) |
Digital sampling frequency |
500Hz |
Digital filtering strategy |
Continues 3 times |
Isolation |
Optical Isolated,3k VDC or 2k Vrms |
Digital Output | |
Type |
Sink or Relay |
I/O Mode |
DO or Relay or Pulse Output |
Pulse Output Frequency |
10Hz~300KHz(Only the 1st Channel can be used as high speed pulse outputs) |
over-Voltage Protection |
50 VDC |
over-Temperature Shutdown |
175C (typical), 150C (min.) |
Load Current |
Max. 500 mA per channel |
Digital sampling frequency |
500Hz |
Isolation |
If DO is Sink type, then no isolation. If it is Relay, then is electrical isolation. |
Analog Input | |
Type |
Differential input |
Resolution |
12 bits |
I/O Mode |
Voltage / Current (jumper selectable) |
Input Range |
0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA |
Accuracy |
0.1% FSR @ 25C |
Sampling frequency |
20Hz |
Built-in Resistor for Current Input |
162 ohms |
Isolation |
Electrical isolation |
Working Power Requirements | |
Input Voltage |
12~36 VDC, Peak Voltage:+40VDC, Power consumption: Less than 3W; |
Input Current |
139 mA @ 24 VDC |
Power Output | |
Output Voltage |
12~36 VDC |
Output Current |
139 mA @ 24 VDC |
LAN | |
Ethernet |
10/100 Mbps, RJ45 ports |
Protection |
15KV ESD Protection |
Protocols |
Modbus TCP, TCP/IP |
Max. TCP Connection |
5 |
Serial Port | |
RS485 |
MODBUS- RTU Protocol, Modbus-ASCII Protocol |
Protection |
15KV ESD Protection |
Modbus Slave address |
1~255 |
Baud Rate |
1200,2400,4800,9600,19200,38400,57600,115200,128000Bps; |
Mapping registers |
Bit Type: 300 Registers, 16-Bit Type: 300 Registers. |
Physical Characteristics | |
Wiring |
I/O cable max. 14 AWG |
Dimensions |
105 x 88 x 30 mm |
Weight |
under 205 g |
Mounting |
DIN rail or wall |
Environmental Limits | |
Operating Temperature |
Standard Models: -10 to 60C (14 to 140F) |
Storage Temperature |
-40 to 85C (-40 to 185F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
Altitude |
up to 3000 m |
Standard Package
1xEthernet Remote I/O Module
1xUser Manual