Product Main

Quick Details

Usage: Personal
Brand Name: king pigeon
color: bule
GSM Frequency: 850/900/1800/1900Mhz
Power: 9-36VDC
Model Number: RTU5029S
Place of Origin: China (Mainland)
Power Status: 3-phase or single-phase
Backup Battery: 900mAH, last 8hours
Exterior dimension: L70mm*W88mm*H30mm

Specifications

GSM 3 Phase Power Loss Alarm Power Failure Voltage Temperature Humidity Status Monitoring RTU5029S
Model: RTU5029S
Name: GSM 3G 4G LTE Phase Loss Monitoring Alarm
Inquiry Onsite Environment AC Power with a FREE Call from Your Mobile Phone!
Interval Report Onsite Environment Power Status to Your Phone by SMS!
Remote Reset, Remote Reboot, Automatic Reboot Periodicity!
High-Low Temperature Humidity Voltage or Power Failur with SMS Alert!
Support Modbus TCP and Modbus RTU over TCP for Cloud Monitoring!
GSM 3 Phase Power Loss Alarm Power Failure Voltage Temperature Humidity Status Monitoring RTU5029S
GSM 3 Phase Power Loss Alarm Power Failure Voltage Temperature Humidity Status Monitoring RTU5029S
the GSM 3G 4G LTE Phase Loss Monitoring Alarm is special for remotely monitoring onsite  temperature, humidity,AC power, power status through wireless GSM/3G/4G Network. When the 3/Single phase power failure, power voltage or  temperature, humidity exceed high threshold or low threshold value, will send SMS alert to upto 10 preset mobile phone immediately.
Just dial from Authorized User number, the GSM 3G 4G LTE Phase Loss Monitoring Alarm will reject at the first "Ring", no communication cost, and then return the current 3/Single phase status,power status or voltage. Moreover, it can report onsite environment interval or daily.
the GSM 3G 4G LTE Phase Loss Monitoring Alarm can be used for solar power monitoring, DC power voltage monitoring, AC power monitoring, Chicken House, Pig Farm, Class Room, Public Room, Waiting Room, Hospital, Stations, Fresh Food Warehouse, Office, Meeting Room, Laboratory, Library and anywhere that need monitoring 3/Single phase AC power failure and temperature or control temperature in expected range.

Mainly Features of 4G Phase Loss Monitoring Alarm:
1.    Can be operated from anywhere, no distance limitation;
2.    No call charges for inquiry. the GSM 3G 4G LTE Phase Loss Monitoring rejects the call from authorized number then return onsite temperature, humidity,AC power status and power voltage on the first 'ring';
3.    Multiple applications. (3/Single phase status, power status, solar panel, DC voltage,temperature, humidity);
4.    up to 10 authorized phone numbers, 5 can be used to receive SMS,and 5 can be used to call and SMS while alarm occurrence;
5.  1 input  for Temperature & Humidity,AC power status monitoring;
6.    External AC Power status monitoring, AC ON/off will send SMS to authorized phone numbers;
7.    Inbuilt MCU monitoring the DC input Voltage value, measure range is 0-36VDC, no need additional sensor to save cost;
8.    Timer Report-Can setup every x hours automatically send its status/Value to the authorized numbers;
9.    Support remotely read historic data via SMS;
10. Support Modbus TCP and Modbus RTU over TCP protocol for cloud monitoring;
11. Rechargeable Backup Battery inside can last 8hours;
12. Secure - Using caller ID and password for identification, unknown callers are ignored;
13. Programmable by SMS Commands or APPs with password protection;
14. Based on GSM/3G/4G Network, applied to many applications.
15. Remote Reset via SMS, Remote Reboot via SMS, Automatic Reboot Periodicity.
Specifications of the 4G Phase Power Loss Monitoring Alarm:
Parameter item Reference scope
DC Power supply 9~36VDC, recommend 12V DC 1A
Power consumption 12V input  Max. 50mA/Average 30mA
Frequency range 2G :850/900/1800/1900Mhz
3G :W :900/2100Mhz  C :850/1900Mhz  T :850/2100Mhz 
4G LTE

SIM Card Supporting 3V SIM Card
Antenna 50 SMA Antenna interface
Protocol
Mobus TCP and Modbus RTU over TCP
Temp&Humi input AM230X:Temperature from -40 to 80C (0.5C accuracy),Relative Humidity from 0-99RH%, accuracy is 3%.
Power Status 3-phase or single-phase
Alert no. 10 authorized phone numbers
Backup Battery 900mAH, last 8hours
Exterior dimension L70mm*W88mm*H30mm
Net Weight 300 g
Standard Package list of 4G Phase Loss Monitoring Alarm:
Phase Loss Monitoring Alarm X 1
GSM/3G/4G Antenna X 1
Backup Battery X 1 (Inbuilt)
AC/DC adaptor(12V1A) X1
User Manual X 1
Note: the package does not include any SIM card.
GSM 3 Phase Power Loss Alarm Power Failure Voltage Temperature Humidity Status Monitoring RTU5029S