After-sales Service Provided: | Engineers available to service machinery overseas |
---|---|
Certification: | ce |
Weight: | 500kg |
Brand Name: | HOPU |
Condition: | New |
Dimension(L*W*H): | 1.5x1.2x1.7 |
Power(W): | 20 to 60 |
Voltage: | 380 |
Usage: | Transformer Oil |
Model Number: | zyd |
Place of Origin: | China (Mainland) |
Working Pressure: | 0.03 |
Flow: | 100LPM |
material: | stainless steel |
Quick Details
Specifications
HOPU ZYD-I Transformer Oil Regeneration and Reclamation System
as transformer oil ages, it oxidizes and begins to break down. during this time, oil purification which effectively removes moisture, solids and gaseous contamination will not be able to remove other by-products from the aging transformer oil. The by-products of the degradation process include acids, aldehydes, and peroxides, which bind together to form sludge.
Sludge attacks the cellulose insulation, inhibits oil flow and traps heat inside the transformer. Eventually the dielectric gap will be bridged, thus, resulting in failure of the transformer.
Oil Regeneration Extends Transformer Unit Life
Deding mobile regeneration system restores transformer oil by removing acidity, sludge, soluble oil decay products and improves oil colour with Fullers earth treatment technology. When the treatment is complete, the regenerated oil meets or exceeds international standards for new oil with lower acidity and improved tan delta, interfacial tension, and oxidation stability. the cellulose insulation and internal components of the transformer also benefit from the flushing effect of multiple passes of hot regenerated oil, which helps remove decay products and sludge from internal surfaces.
Advantages of Oil Regeneration
Extends the transformer life by restoring the qualities of the transformer oil to be similar to new oil condition
Oil Regeneration is much less costly than changing new oil
Minimal downtime as a result no revenue loss as Oil Regeneration can be performed 'on-inline or live'/ energized transformer
Environmentally friendly as the existing oil is reused. There will also be no hazard from oil spills and PCB contamination, including the trouble with the disposal of old oil
Oil Regeneration removes the sludge build up and deposited on the internal core and coils of the transformer, which a traditional oil change will not
Oil Regeneration can be continuously performed in most weather conditions and will not run the risk of exposing the internal transformer core to adverse weather conditions during an oil change
Technical Parameters
Parameter | Unit | ZYD-I-30 | ZYD-I-50 | ZYD-I-100 | ZYD-I-150 | ZYD-I-200 | ZYD-I-250 | ZYD-I-300 |
Flow rate | L/h | 1800 | 3000 | 6000 | 9000 | 12000 | 15000 | 18000 |
Working vacuum | MPa | -0.07~-0.099 | ||||||
Working pressure | MPa | 0.5 | ||||||
Temperature | 30 ~ 80 | |||||||
Power | 3 ph 380V 60Hz (or please contact HOPU'S presentives) | |||||||
Working noise | DB(A) | 60 | 65 | 70 | 75 | 78 | 80 | 85 |
Heating power | kW | 30 | 36 | 48 | 60 | 80 | 108 | 120 |
Total power | kW | 36 | 44 | 54 | 66 | 93 | 120 | 135 |
Oil Inlet/Outlet | mm | 32 | 32 | 42 | 42 | 48 | 60 | 76 |
Weight | Kg | 850 | 1000 | 1200 | 1600 | 2200 | 2600 | 3000 |
Size | L,mm | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 |
W,mm | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |
H,mm | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
Oil Index after Treated by ZYD-I Machine
Item | Unit | after treatment |
Breakdown Voltage | kV | 75 |
Moisture content | PPM | 3 |
Gas content | % | 0.1 |
Impurity size | Micron | 0.5 (no free carbon) |
IFT | Dynes/cm | 40 |
Acid value | Mg KOH/g | 0.03 |
Dielectric loss factors | Tg(90C) | 0.001 |
Colour | L | 0.5 |