After-sales Service Provided: | Engineers available to service machinery overseas |
---|---|
Brand Name: | Yuneng |
Certification: | CE, ISO |
Model Number: | QTHS-1-2, QTHS-1-10, QTHS-1-15, QTHS-1-30, QTHS-1-60 |
Place of Origin: | China (Mainland) |
Product name: | SF6 Gas Reclaiming Plant untuk Pemurnian dan Pengisian |
Power: | 5KW~22KW |
Filling final pressure: | 0~0.8MPa Adjustable |
Gasification way: | Electric heating |
Liquefaction way: | High pressure condensation liquefaction |
Dry filter regeneration mode: | Vacuum activation regeneration |
Gas purity: | 60PPM |
Oil content: | 5PPM |
Impurities: | 1 micron |
Usage: | SF6 Gas Reclaiming Plant untuk Pemurnian dan Pengisian |
Quick Details
Specifications
SF6 Gas Reclaiming Plant untuk Pemurnian dan Pengisian
Gas recovery, purification and filling equipment widely used in SF6 gas insulated electrical equipment factory, use, operation, scientific research departments and so on, to create vacuum for a variety of electrical equipment, and fill electric wquipment with SF6 gas, and recover SF6 gas from use or test equipment, then fill to storage tank after purifying and compressing. The recovery device is suitable for SF6 electrical appliance and GIS combined electrical apparatus. The gas recovery unit of SF6 is based on the standard of DL/T662-2009 "SF6 gas filling and recovery device", which consists of recovery system, and inflating system, vacuum system, purification system and gas storage system.
1. Vacuumize and check vacuum pressure for retrieving device itself including its storing vessel and pipes;
2. Vacuumize and check vacuum pressure for the insulation equipment
3. Retrieve and store SF6 gas and check the remaining vacuum pressure of the insulation equipment;
4. Get rid of water content and other particulates in the SF6gas with filtration and purification process;
5. Refill up the SF6 gas into the insulating equipment to specified operating pressure.
Item | Name of Parameter | Unit | Model | ||||
QTHS-1-2 | QTHS-1-10 | QTHS-1-15 | QTHS-1-30 | QTHS-1-60 | |||
Technical parameter of the equipment | Capacity | m/h | 2 | 10 | 15 | 30 | 60 |
Recovery pressure | MPa | 0.05 | |||||
1m gas recovery time (initial pressure 0.6MPa) | h/m | 3 | 0.6 | 0.4 | 0.2 | 0.1 | |
Final pressure | MPa | 0~0.8 Adjustable | |||||
1m gas injection time(initial pressure 133Pa to 0.6MPa) | h/m | 3 | 0.6 | 0.4 | 0.2 | 0.1 | |
the time required for 1m volume vacuity from 0.1MPa to 133Pa | h | 1 | 0.6 | 0.4 | 0.4 | 0.4 | |
Ultimate vacuum | PA | 10 | |||||
Gasification way | Electric Heating | ||||||
Liquefaction way | High pressure condensation liquefaction | ||||||
Dry filter regeneration mode | Vacuum activation regeneration | ||||||
External dimensions(including storage tank rack) | mm | 1000*800*1500 | 1600*1200*1800 | 1800*1200*1800 | 1800*1200*1800 | 2300*15800* 2000 | |
Working power | V | (380V-50Hz) 3Phase 4 Wires, or as per buyer's option | |||||
Total electrical power | KW | 5 | 8 | 12 | 18 | 22 | |
Index | SF6 Gas purity after recovery | PPM | 60 | ||||
Oil content | PPM | 5 | |||||
Impurities | m | 1 |