| Type: | 50Hz to 400Hz Converters |
|---|---|
| Output Voltage: | 400Hz 3-Phase 200/208V |
| Input Voltage: | 50Hz 3-Phase 380V |
| Output Type: | Single |
| Brand Name: | IDEAL |
| Output Current: | 55.5A |
| Output Frequency: | 400Hz |
| Model Number: | ADBF400Y4-20 |
| Place of Origin: | China (Mainland) |
| Input Frequency: | 50Hz |
| Pole of Motor: | 4 poles |
| Pole of Generator: | 32 poles |
| Mounting Structure: | Common-Shaft Mounting |
| THD: | 1.5% |
| Crest Factor: | 1.31-1.51 |
| Insulation: | H |
| Protection: | IP23/IP44/IP54 |
| Type of Motor: | Induction Motor |
| Type of Generator: | Brushless Synchronous Generator |
Quick Details
Specifications
Description
Product Name: Motor Generator Set (Rotary Frequency Converter) 50Hz to 400Hz Induction Type
Model No. ADBF400Y4
Motor Type: Induction Motor
Input Frequency: 50Hz
Output Frequency: 400Hz
Rated Speed: 1500rpm
Rating Range: 10-50kVA
General Introduction
the ADBF400Y4 series Motor Generator Sets consist of a 4-pole induction motor and a 32-pole synchronous generator. the motor and the generator are mounted on the common shaft (integrative mounting) and operate at the speed of 1500rpm. the products are designed for airport ground power units which require a clean 400Hz power output converting from the 50Hz grid line.
the ADBF400Y4 Motor Generator Sets are rated for continuous duty. They have prominent technical advantages on reliable excitation, precise voltage regulation, outstanding voltage waveform, compact size, easy operation and no radio interference. They also have the high overload capability, best transient characteristics and rugged fabrication, which make them suitable for the applications where continuous service in a harsh environment is required.
as an option, ADBF400Y4 series Motor Generators can be mounted with a weather-proof enclosure, an acoustic-attenuated canopy or a trailer.
Technical Data
MG Set Parameters | |||||
| Model No. | ADBF400Y4-10 |
ADBF400Y4-20 | ADBF400Y4-30 | ADBF400Y4-40 | ADBF400Y4-50 |
| Rated Power |
10kVA/8kW | 20kVA/16kW | 30kVA/24kW | 40kVA/32kW | 50kVA/40kW |
| Power Factor |
0.8 (lag) | ||||
| Duty Cycle |
S1 (continuous) | ||||
| Insulation |
Class H | ||||
| Protection | IP23 | ||||
| Operation Noise | ≤55dB(A)/1m | ||||
| Mounting Structure |
the motor and the alternator are mounted on the single shaft (integrated mounting). | ||||
| Overload Capacity |
110% rated load for 1 hour continuous in every 12 hours. | ||||
| Temperature Rise |
No more than 90°C Rise in ambience 40°C measured by resistance | ||||
| Ventilation |
Shaft-mounted fan | ||||
| Rotor Balancing |
G1.0 Grade as per ISO1940-1 | ||||
| Ambient Temperature | -15°C to +40°C maximum without de-rating | ||||
| Altitude |
1000m | ||||
| Relative Humidity | 95% with no condensation | ||||
| Compliance |
IEC60034, NEMA MG1, MIL-STD-704F & China National Standards | ||||
Generator Parameters | |||||
| Rated Frequency |
400Hz | ||||
| Pole Count |
32 poles | ||||
| Rated Speed |
1500rpm | ||||
| Rated Voltage | 3-phase 208V (line to line) | ||||
| Winding Connection |
Wye with neutral | ||||
| Rated Current |
27.8A |
55.5A | 83.3A | 111.0A | 138.8A |
| Excitation Mode | Automatic self excitation with AVR control | ||||
| Steady Voltage Regulation | Within ±1% (0 to 100% steady state, balanced, linear load) | ||||
| Transient Voltage Regulation | Within ±12% (0 to 100% rated load applied or removed in one single step) | ||||
| Voltage Recovery Time | ≤ 0.1s | ||||
| Harmonic Distortion | THD ≤ 1.5%, single harmonic ≤ 1.2% | ||||
| Crest Factor | 1.31-1.51 | ||||
Motor Parameters | |||||
| Motor Type | Induction Motor | ||||
| Motor Power | 15kW | 22kW | 30kW | 37kW | 55kW |
| Rated Freqency | 50Hz | ||||
| Rated Speed | 1460rpm | 1470rpm | 1470rpm | 1475rpm | 1480rpm |
| Pole Count | 4 poles | ||||
| Rated Voltage | 3-phase 380V (line to line) | ||||
| Rated Current | 30.1A | 43.4A | 57.9A | 71.4A | 103.8A |
| Winding Connection | Delta | ||||
| Power Factor | 0.86 | 0.86 | 0.87 | 0.87 | 0.88 |
| Efficiency | 88.0% | 89.5% | 90.5% | 90.5% | 91.5% |
| Starting Mode | Wye-Delta reduced voltage starting | ||||
| Frequency Regulation | Within ±1.0% from no load to full load | ||||
Options
- WeaTher-proof / sound-proof enclosure
- Analog control panel
- Digital control panel
- Trailer / trolley
Typical Structure
Outline Dimensions
Model No.
A
AB
AC
B
BD
C
H
HD
L ADBF400Y4-10
326
410
407
306
448
255
230
630
890 ADBF400Y4-20
407
448
300
230
630
970 ADBF400Y4-30
407
448
300
230
630
1020 ADBF400Y4-40
427
468
340
250
680
1050 ADBF400Y4-50
457
498
380
250
680
1130
Technical Features