Usage: | electrical testing equipment |
---|---|
Power: | Electronic |
Brand Name: | GFUVE |
Warranty: | 3 years |
weight: | 27kg |
Model Number: | GF302D |
Place of Origin: | China (Mainland) |
AC Voltage Output: | 57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional) |
AC Current Output: | 200mA, 1A, 5A, 20A, 100A |
Phase Output: | 0-359.999 |
Power Factor: | -1 ~ 0 ~ 1 |
Frequency Output: | 45Hz-65Hz |
Harmonic: | 2-51times |
Accuracy: | 0.05%, 0.1% |
Dimensions (W*D*H) (mm)Dimensions (W*D*H) (mm): | 500*600*175 |
Weight: | 27kg |
Quick Details
Specifications
FEATURES
- Able to test basic error, shunt running, start, standard error automatically and manually in single-step of single/three phase, according to relative regulation of kWh meter.
- Able to do change test caused by voltage influence, frequency influence and harmonic influence.
- Output of power source is speedy and stable, AC maximum output of each phase can reach 120A in maximum.
- Voltage, current and phase position of each phase can be adjusted in split-phase, improving the flexibility of power source.
- Frequency of each impulse input port can reach 40Hz.
- 7-inch TFT color display touch screen, English menu, simple and convenient operation, commonly used functions and current basic load point can be controlled in one button.
- Each meter position can provide one standard, dependent RS485 port, and able to perform multi-function test, such as communication test.
- Impulse port of each meter position, external polarity can be set randomly, able to adapt kWh meter of impulse cascade and common-anode.
Electrical parameters | |
---|---|
Accuracy | 0.05%, 0.1% |
Power Supply | One Phase AC 180-265V, frequency 50/60Hz. |
AC Voltage Output | |
Range(U1,U2,U3) | 57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional) |
Adjustment range | (0-120)%RG(1) |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | 0.01%/120s |
Distortion | 0.3% (Non-capacitive load) |
Output load | Each phase 25VA |
Measuring accuracy | 0.05%RG |
AC Current Output | |
Range(I1,I2,I3) | 200mA, 1A, 5A, 20A, 100A |
Adjustment range | (0-120)%RG |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | <0.01%/120s |
Distortion | ≤0.3% (Non-capacitive load) |
Output load | 45VA |
Accuracy | 0.05%RG |
Power Output | |
Active power output stability | <0.01%RG/120s |
Reactive power output stability | <0.02%RG/120s |
Active power measuring accuracy | 0.05%RG |
Reactive power measuring accuracy | 0.1%RG |
Phase Output | |
Output adjustment range | 0°-359.999° |
Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
Resolution | 0.01° |
Accuracy | 0.05° |
Power Factor | |
Adjustment range | -1 ~ 0 ~ 1 |
Resolution | 0.0001 |
Measurement accuracy | 0. 0005 |
Frequency Output | |
Adjustment range | 45Hz-65Hz |
Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
Resolution | 0.001Hz |
Accuracy | 0.005Hz |
Voltage /Current/Harmonic Setting | |
Harmonic number | 2-51times |
Harmonic content | 0-40% |
Harmonic phase | 0-359.99 |
Harmonic setting accuracy | (10%±0.1%)RD(2) |
Power Energy Measurement Error | |
Active power energy | 0.05%RG |
Reactive power energy | 0.1%RG |
Power Pulse Output | |
Power pulse type | Active pulse, reactive pulse |
Active power pulse output | 5V, 10mA |
Power Pulse Input | |
Energy pulse type | Support active and reactive pulse, the highest frequency power pulse input is 180K. |
Mechanical parameters | |
Dimensions (WDH) (mm) | 500x600x175 |
Weight (kg) | about 27 |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |