| Measurement Type: | Current, Inrush Current, Voltage |
|---|---|
| Width: | 180mm |
| Length: | 240mm |
| Absolute Maximum Current Measurement: | 100 A ac, 100 A ac/dc, 1000 A ac, 10000 A ac, 1300 A ac/dc, 200 A ac |
| Measurement Standards: | IEC 610101 |
| Minimum Frequency: | 40 Hz |
| Interface Type: | USB |
| Brand: | Chauvin Arnoux |
| Weight: | 1.9kg |
| Power Source: | Battery, Mains |
| Dimensions: | 240 x 180 x 55mm |
| Maximum Frequency: | 69Hz |
| Number of Phases: | 1, 3 |
| Height: | 55mm |
| Battery Type: | Rechargeable NiMH |
| Maximum Voltage: | 1000V |
| Battery Life: | 13 h |
| Model Number p: | CA8333 |
| Display Type: | TFT LCD |
Quick Details
Specifications
Designed for maintenance and test departments working in industrial or administrative buildings, the CA 8333 QualiStar Plus can be used to obtain a snapshot of the main features characterizing the quality of the electrical network. Easy to handle and compact, the QualiStar+ offers a large number of calculated values and several processing functions.
For sizing installations or troubleshooting switching faults, the CA 8333 Power Quality Analyser is equipped with a transient mode which allows users to measure the inrush current over 4 periods
The CA 8333 captures and records all the parameters, transients, alarms and waveforms simultaneously
Large colour TFT screen for easy reading
TRMS AC+ DC voltage up to 1000 V
TRMS AC+ DC current: 5 mA to 10 kA depending on the sensors
Frequency
Power values: W, VA, var, VAD, PF, DPF, cos φ, tan φ
Energy values: Wh, varh, VAh, VADh, BTU, toe, Joule
Harmonics from 0 to the 50th order, phase
Transients: up to 50
Inrush over 4 periods
Recording of a selection of parameters at the maximum sampling rate for several days to several weeks
Alarms: 4000 of 10 different types
Peak detection
Vectorial representation
Available in more than 27 languages
IP53 / IK08
USB communication
IEC 61000-4-30 Class B
For sizing installations or troubleshooting switching faults, the CA 8333 Power Quality Analyser is equipped with a transient mode which allows users to measure the inrush current over 4 periods
The CA 8333 captures and records all the parameters, transients, alarms and waveforms simultaneously
Large colour TFT screen for easy reading
TRMS AC+ DC voltage up to 1000 V
TRMS AC+ DC current: 5 mA to 10 kA depending on the sensors
Frequency
Power values: W, VA, var, VAD, PF, DPF, cos φ, tan φ
Energy values: Wh, varh, VAh, VADh, BTU, toe, Joule
Harmonics from 0 to the 50th order, phase
Transients: up to 50
Inrush over 4 periods
Recording of a selection of parameters at the maximum sampling rate for several days to several weeks
Alarms: 4000 of 10 different types
Peak detection
Vectorial representation
Available in more than 27 languages
IP53 / IK08
USB communication
IEC 61000-4-30 Class B