| Operating Temperature Range: | -10 → +60 °C |
|---|---|
| Width: | 66mm |
| Reset Method: | Automatic, Manual, Remote |
| Mounting Style: | DIN Rail Mount, Surface Mount |
| Brand: | ABB |
| Minimum Operating Temperature: | -10°C |
| Maximum Operating Temperature: | +60°C |
| Control Voltage: | 240 V |
| Terminal Type: | Screw |
| Contact Current Rating: | 32 A |
| Series: | DMPO |
| Range: | DM Range |
| FLC Motor Rating: | 0.2 → 32 A |
| Supply Voltage: | 220 V ac |
| Length: | 84mm |
| Depth: | 116mm |
Quick Details
Specifications
Protection of 3-phase loads e.g. cage induction motors.They monitor current flowing in 2 of the 3 lines and in the event of an overload condition the output relay will de-energise after a time delay inversely proportional to the overcurrent. The units will tolerate a wide (> 2:1) variation in supply voltage without loss of performance
0.2 - 32A FLC in one unit
Integral current transformers
Selectable starting delay for high inertia loads
Trip and alarm contacts
Supply, warning and trip indication
Auto/manual/local/remote reset
Delayed or instantaneous reset
Test facility
Product can be used for loads above 32A with use of external CTs
Retentive trip memory version available (latching)
0.2 - 32A FLC in one unit
Integral current transformers
Selectable starting delay for high inertia loads
Trip and alarm contacts
Supply, warning and trip indication
Auto/manual/local/remote reset
Delayed or instantaneous reset
Test facility
Product can be used for loads above 32A with use of external CTs
Retentive trip memory version available (latching)