| Minimum Operating Temperature: | -10°C |
|---|---|
| Maximum Operating Temperature: | +70°C |
| Maximum Control Voltage: | 280 V ac/dc |
| Series: | DRH |
| Mounting Type: | DIN Rail |
| Capacitance: | 20pF |
| Minimum Load Voltage: | 48 V ac |
| Minimum Control Voltage: | 90 V ac/dc |
| Relay Type: | Solid State Relay |
| Height: | 86.7mm |
| Number of Poles: | 3 |
| Maximum Turn On Time: | 30 ms |
| Depth: | 95.6mm |
| Maximum Load Current: | 18 A rms |
| Maximum Load Voltage: | 600 V ac |
| Off State Leakage Current: | 3 mArms |
| Load Voltage Range: | 48 → 600V ac |
| Length: | 45.3mm |
| Standards Met: | CCCs, CE, CSA C22.2 No. 14, cULus Listed E116949, EMC Compliant, EN/IEC 60947-4-2, IEC, IEC 60068-2-27, IEC 60068-2-6, IEC 61000-4-2, IEC 61000-4-4, UL |
| Brand: | Sensata / Crydom |
| Switching Type: | Zero Crossing |
| Operating Temperature Range: | -10 → +70°C |
| Minimum Load Current: | 150 mA |
| Special Features: | AC or DC Control, Alarm Output in Case of Over-Temperature, Built-In Overvoltage Protection, Fan Controlled Through Thermistor & Microprocessor to Optimize Fan Operation, Horsepower Rated, Integrated Over-Temperature Protection, Multicolor LED with Input Status & Alarm Indicator |
| Dimensions: | 45.3 x 95.6 x 86.7mm |
| Terminal Type: | Screw |
| Control Voltage Range: | 90 → 280 V ac/dc |
Quick Details
Specifications
Crydom DRH series DIN Rail mount solid-state contactors with ratings up to 20 A per channel at 600 V ac. The DRH Series is ideal for heating applications and can be used to control (start/stop) 3 phase motors of up to 5 HP at 480 V ac. It is an effective solution for replacement of electromechanical contactors in commercial and industrial applications that require frequent switching.
DRH Series contactors have an innovative design that increases the airflow thus improving thermal performance. Featuring over-temperature protection to avoid overheating in case of a fan malfunction.
Over-voltage protection Alarm output in case of over-temperature
Enclosed heat sink
Zero voltage and instantaneous turn-on output
Multicolour LED with input status and alarm indication
cULus listed and CE compliant
Ratings up to 20 A at 600 V ac
Fits standard 35 mm DIN Rail
Fan controlled through thermistor and microprocessor to optimise fan operation
Over-voltage protection Alarm output in case of over-temperature
Enclosed heat sink
Zero voltage and instantaneous turn-on output
Multicolour LED with input status and alarm indication
cULus listed and CE compliant
Ratings up to 20 A at 600 V ac
Fits standard 35 mm DIN Rail
Fan controlled through thermistor and microprocessor to optimise fan operation