Product Main

Quick Details

Operating Temperature Range: -20 → +60 °C
Frequency Sensing Range: 40 → 60 Hz, 50 → 70 Hz
Frequency Sensitivity: Underfrequency
Width: 45mm
Time Delay: 200 ms
Brand: Broyce Control
Minimum Frequency Sensed: 40Hz
Contact Configuration: DPDT
Maximum Frequency Sensed: 60 Hz, 70 Hz
Monitoring Application: Frequency
Minimum Operating Temperature: -20°C
Maximum Operating Temperature: +60°C
Height: 78mm
Electrical Phase: 1
Dimensions: 99 x 45 x 78 mm
Supply Voltage: 230 V ac
Length: 99mm

Specifications

This Broyce Control 45UFR electrical relay unit is designed to monitor the frequency of its own supply. The 45UFR is used for monitoring under frequency conditions, whereby the relay de-energises when the frequency drops below the adjustable trip point. The relay re-energises when the frequency increases above the trip point plus the hysteresis.
Detects Under frequency
UFR relay de-energises if frequency falls below trip level – red LED on, contacts 11, 14 /21 & 24 closed
Adjustable trip level
Adjustable hysteresis
Monitors own supply
1 x DPDT relay output 8A
LED indication for supply and relay status
DIN rail housing
Write on identification tab
Dimensions: H78 x W45 x D99mm