| Drain Wire: | No |
|---|---|
| Minimum Operating Temperature: | -40°C |
| Insulation material: | PVC |
| Maximum Operating Temperature: | +80°C |
| Conductor Material: | Copper |
| Standards Met: | CE |
| Screened/Unscreened: | Unscreened |
| Sheath Material: | Polyvinyl Chloride PVC |
| Sheath Colour: | Blue |
| Cross Sectional Area: | 1.5 mm² |
| Hazardous Area Certification: | ATEX |
| Brand: | Lapp |
| Length: | 50m |
| Outer Diameter: | 8.1mm |
| American Wire Gauge: | 15 AWG |
| Screen Type: | Unscreened |
| Minimum Bend Radius: | 6 x Diameter |
| Series: | ÖLFLEX EB |
| Number of Cores: | 5 |
| Voltage Rating: | 500 V |
| Fire Behaviour: | Flame Retardant |
Quick Details
Specifications
?lflex? EB is a PVC control cable with a blue outer sheath for use in explosive atmospheres with hazard type "i" (intrinsically safe). Complies with DIN EN 60079-14 section 12.2.2 (VDE 0165 Part 1).
Designed in accordance with HD 21.13 that is VDE 0281-13
Conductor: fine wire strand of bare copper to IEC 60228 (VDE 0295) class 5
Core insulation: PVC compound TI2 in accordance with VDE 0281 part 1 (HD 21.1 S3)
Identification: in accordance with HD 186 that is VDE 0293; black cores with white numbers, with or without green/yellow ground conductor
Wrapping: Insulating plastic
Outer sheath: Blue PVC compound TM2 in accordance with HD 21.1 S3 that is VDE 0281 part 1
Test voltage: 3000Vac
Temperature range: -5°C → +70°C (flexible installation); -40°C → +70°C (static installation)
Minimum bending radius: 15 x cable diameter (flexing)
Flame retardant in accordance with IEC 60 332.1
Tested in accordance with VDE 0472 and IEC 60 811-X.X that is VDE 0473
Designed in accordance with HD 21.13 that is VDE 0281-13
Conductor: fine wire strand of bare copper to IEC 60228 (VDE 0295) class 5
Core insulation: PVC compound TI2 in accordance with VDE 0281 part 1 (HD 21.1 S3)
Identification: in accordance with HD 186 that is VDE 0293; black cores with white numbers, with or without green/yellow ground conductor
Wrapping: Insulating plastic
Outer sheath: Blue PVC compound TM2 in accordance with HD 21.1 S3 that is VDE 0281 part 1
Test voltage: 3000Vac
Temperature range: -5°C → +70°C (flexible installation); -40°C → +70°C (static installation)
Minimum bending radius: 15 x cable diameter (flexing)
Flame retardant in accordance with IEC 60 332.1
Tested in accordance with VDE 0472 and IEC 60 811-X.X that is VDE 0473