| Coil Number: | Autotransformer |
|---|---|
| Coil Structure: | Toroidal |
| Phase: | Three |
| Usage: | Electronic |
| Brand Name: | TYC |
| Model Number: | TY-6630 |
| Place of Origin: | China (Mainland) |
Quick Details
Specifications
I Introduction
the MOA characteristic tester is used for the measurement and analysis of metal oxide arrester [MOA] leakage. Widely use in measuring the resistive Current to analyze the degree of zinc oxide arrester field Monitor and test in Lab.this tester adopts microcomputer sampling, control and other advanced Technology, IT can test zinc oxide Arrester in the power frequency voltage of the full current, third harmonic, Resistive current, resistive current peak, capacitive current, active power, Etc..and display voltage, current waveform and print out test data. At the same Time provide the field waveform display.The instrument has the characteristics of simple connection, high measuring accuracy and strong reliability.The Instrument is small in size and light in weight, and adopts integrated design, Which is easy to carry and operate in the field.
II Performance
1, Lar-screen LDC display by 1024X600.
2, high precision sampling, processing Circuit, advanced Fourier harmonic analysis technology, more reliable data.
3, Equip Test harmonic content , also can Test single-phase or tri-phase Measurement simultaneously
4, Equip resistive current base wave Peak output function.
5,Built-in large capacity memory. Storage test data, waveform, harmonics and other large amount of record Information.It can save 200 groups of measurement records in the cycle update Mode.
6, Store any group of test records through USB Interface, the instrument Is (the capacity is limited by the size of U disk).
7. Equip insurance to avoid Misconnection. the voltage and current plug of the instrument has the function of misinsertion prevention.
8. Equip wireless module, which can carry out Wireless voltage acquisition and wireless measurement with the host.
9, Built-in high precision real-time Clock, can carry out date and time calibration.
10. Equip a high-speed miniature thermal printer, which Can print the measurement data.
11, Built-in large capacity lithium Battery, can work continuously for 6 hours.
12, Connect phone Bluetooth, remote control
III Technical Parameter
Voltage and current parameter
Test detail |
Test range |
Test precision |
Full current |
0-20mA |
±(reading5%+5uA) |
Impedance current |
0-20mA |
±(reading5%+5uA) |
Capacitive current |
0-20mA |
±(reading 5%+5uA) |
Current harmonics |
0-20mA |
±(reading10%+10uA) |
Reference voltage |
Max 400V |
±(reading5%+0.5V) |
Voltage harmonics |
Max 400V |
±(reading10%) |
2, Temperature: -10℃40℃
3, Ambient Humidity: ≤85% Non- condensation
4, Storage Temperature : -20℃50℃
5, Size: 252*160*65(mm)
Device weight : 5kg (not include testing wire and wire box)