Product Main

Quick Details

Brand Name: gdmk
color: other
Elongation at Break: output frequency30 300Hz
Min. Bending Radius: Quality factor30~90
Consistency of rod: Instability0.05%
Model Number: TKBPXZ
Place of Origin: China (Mainland)
Quality factor: 30~90

Specifications

Product DescRiption

       
        Transformer GIS SF6 switch CT/PT insulator bus bar cable bushing and others capacitive devices are the common primary electric equipments.
        the complete set of frequency conversion series resonance test equipment is mainly used for AC withstand voltage test of cross-liNked cable, hydraulic generator, main transformer, bus GIS etc. 
       the complete set of frequency conversion series resonance test equipment is mainly composed of frequency conversion control power, supply excitation, transformer reactor, capacitor voltage divider and compensation capacitor (optional).

  

Product features 
  • 1, the reactor of the same voltage grade and capacity has smaller volume and lighter weight. Small temperature rise at rated load; Dry pouring high mechanical strength good electrical insulation beautiful and reliable.

  • 2, Large capacity margin of frequency conversion power control box; Strong protection function; Good output waveform; Good stability; with a variety of working modes easy to operate; Single-phase 220V or three-phase 380V input power supply is common which is convenient for on-site power collection.

  • 3, Flexible configuration. Can choose different types of reactor meet the requirements of different test products achieve a multi-purpose cost-effective.


Product Parameters
Technical parameter
Rated output voltage 01000kV and below
Output frequency 30300Hz
Resonance voltage waveform Pure sine wave waveform distortion rate≤1.0%
Working time Full power continuous working time of 60min
Quality factor 30~90
Frequency regulation sensitivity 0.1Hz
Instability 0.05%
Working power supply Single-phase 220V or three-phase 380V±10%
Power frequency 50Hz±5%
Serial product configuration(Application range (10kV ~ 500kV voltage grade substation electrical equipment AC withstand voltage equipment frequency 30 ~ 300Hz))
Product model name Variable frequency source Resonant reactor Exciter transformer Voltage divider Scope of application
TKBPXZ-50/50 4kW 25kV/1A two(dry) 4kVA(dry) 50kV 1000kVA and below 10kV power transformer. 10kV switch bus PT CT etc. 10 kv (300mm2) cable 1.0 km or less
TKBPXZ-108/108 6kW 27kV/1A four(dry) 6kVA(dry) 110kV 31500kVA and below 35kV power transformer. 35kV switch bus PT CT etc. 10 kv (300 mm2)cable≤2km.35kV (300mm2)cable≤0.5km
TKBPXZ-200/200 10kW 50kV/1A four(dry) 10kVA(dry) 200kV 50000kVA and below 110kV power transformer.110kVGIS, PT, CT etc.(Preventive test).35kV(300mm2)cable≤1.0km.10kV (300mm2)cable≤2.0km
TKBPXZ-270/270 15kW 45kV/1A Six sets of(dry) 15kVA(dry) 300kV 50000kVA and below 110kV power transformer.110kVGIS, PT, CT etc..35kV(300mm2)cable≤1.2km.10kV (300mm2)cable≤3.0km
TKBPXZ-800/400 30kW 50kV/2A eight(dry);
100kV/2A four(oil-immersed)
30kVA(dry);
30kVA(oil-immersed)
400kV 80000kVA and below 220kV power transformer.50000kVA and below 110kV power transformer.110kV/220kVGIS, PT, CT etc..35kV(300mm2)cable≤2.0km.110kV (300mm2)cable≤0.7km
TKBPXZ-1600/800 60kW 200kV/2A four(oil-immersed) 60kVA(dry) 800kV 220kV power transformer of 80000kVA and below.50000kVA and below 110kV power transformer.500kVGIS, PT, CT etc..220kV switch, GIS, PT, CT etc..110kV(400mm2)cable≤1.5km.220kV (400mm2)cable≤1.0km
TKBPXZ Variable Frequency Series AC Resonant Test System