| Application: | Computer |
|---|---|
| Type: | On-line |
| Protection: | Overvoltage |
| Phase: | Single Phase |
| Brand Name: | Wahbou |
| Output Voltage: | 220Vac 1P2W+G |
| Weight: | 9.5kg |
| Model Number: | XT 1KVA |
| Place of Origin: | China (Mainland) |
| Rated Power: | 1kVA/0.9kW |
| Input Voltage Range: | 90-285Vac 1P2W+G |
| input Working Frequency Range: | 40-70Hz (settable) |
| Input Power Factor: | 0.99 |
| Output Frequency: | 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery) |
| Output Power Factor: | 0.9 |
| Conversion time between Mains Power and Battery: | 0ms |
| Battery Rated Voltage: | 24Vdc |
| Battery Quantity: | 2 |
| Dimension (LxWxH) mm: | 350x144x230mm |
Quick Details
Specifications
PARAMETER XT 1-3KVA
| Model | XT 1KVA | XT 1KS | XT 2KVA | XT 2KS | XT 3KVA | XT 3KS | |
| Rated Power | 1kVA/0.9kW | 2kVA/1.8kW | 3kVA/2.7kW | ||||
| Input | Voltage Range | 90-285Vac 1P2W+G | |||||
| Working Frequency Range | 40-70Hz (settable) | ||||||
| Input Power Factor | ≥0.99 | ||||||
| Output | Rated Voltage and Accuracy | 220Vac(1±2%) 1P2W+G | |||||
| Output Frequency | 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery) | ||||||
| Rated Current | 4.5A | 9.1A | 13.6A | ||||
| Output Power Factor | 0.9 | ||||||
| Output Harmonic Wave | ≤4% | ||||||
| Crest Factor | 3: | 1 | |||||
| Output Overload | 105%±5%Load≤125%±5%: Convert to bypass output and alarm after 50s; 125%±5%Load≤150%±5%: Convert to bypass output and alarm after 25s; Load150%±5%: Convert to bypass output and alarm after 300ms. | ||||||
| Conversion time between Mains Power and Battery | 0ms | ||||||
| Efficiency | ≥85% | ||||||
| Battery | Rated Voltage | 24Vdc | 36Vdc | 48Vdc | 72Vdc | 72Vdc | 96Vdc |
| Quantity | 2 | 3 | 4 | 6 | 6 | 8 | |
| Charging Current | 1A | 6.5A | 1A | 5.5A | 1A | 5.5A | |
| Dimension (LxWxH) mm | 350x144x230 | 425x190x328 | |||||
| Weight | 9.5kg | 6kg | 18.5kg | 10kg | 23.5kg | 11kg | |
| Working Temperature | 0℃-40℃ | ||||||
| Working Humidity | 20%-95% | ||||||
| Noise | ≤50dB | ||||||