Features:
1) Multiple CPU intelligent controls
2) Advance IGBT inverted technology
3) Advance control design structure
4) Intelligent by-pass switch
5) Personal display interface
6) Battery switch-on function
7) Advance phase-balanced technology
8) Sole parallel redundant structure
Specifications:
1) Mode: ST6K-400K (three in and three out)
2) Capacity (kW): 6-400kVA
3) Input voltage: three phases with four wires, 380V?5%
4) Battery DC voltage:
a) 6-20kVA: 192V
b) 30-400kVA: 336V
5) Noise:
a) 6-20kVA: ≤53dB, 1m distance
b) 30-60kVA: ≤56dB, 1m distance
c) 80-150kVA: ≤65dB, 1m distance
d) 200-400kVA: ≤68dB, 1m distance
6) Dimensions (W x D x H):
a) 6-20kVA: 550 x 600 x 1,135mm
b) 30-60kVA: 650 x 700 x 1,510mm
c) 80-150kVA: 1,250 x 750 x 1,600mm
d) 200-400kVA: 1,600 x 750 x 1,600mm
7) Weight (excluding battery):
a) 6kVA: 260kg
b) 10kVA: 280kg
c) 15kVA: 310kg
d) 20kVA: 340kg
e) 30kVA: 480kg
f) 40kVA: 520kg
g) 50kVA: 560kg
h) 60kVA: 580kg
i) 80kVA: 780kg
j) 100kVA: 860kg
k) 120kVA: 980kg
l) 150kVA: 1,250kg
m) 200kVA: 1,600kg
n) 250kVA: 1,800kg
o) 300kVA: 2,100kg
p) 400kVA: 2,500kg
8) Input frequency: 50Hz/60Hz?0%
9) Input power actor: ≥95%
10) Output voltage: three phases with four wires, 380V?%
11) Output frequency: 50Hz?.05% (when power is provided by battery)
12) Output harmonic distortion: pure sine wave, distortion factor <3% (linear load)
or <5% (non-linear load)
13) Output unbalanced voltage: balanced load ≤1%, unbalanced load ≤3%
14) Output phase displacement angle: balanced load ≤1? unbalanced
load≤3?
15) Output dynamic transient range: when output is 0-50%-100%≤3%, recovery
time is ≤10ms
16) Output overload capacity:
a) 125%: ≥10min
b) 150%: ≥20s
17) Output peak factor:5:1
18) Output switching time: pure online zero switching
19) System performance MTBF: 300,000 hours
20) Temperature: -10~50?
21) Humidity: 0-93% (no condensation)
22) Altitude: ≤3,000m
23) Supported software interface: Novell Net Ware, Microsoft Windows9X,
Windows2000, Windows NT