Main features
Combined electronic type RCD/MCD device
High breaking capacity:10KA
Line voltage-independent tripping
Compatible with standard busbar
Twin-purpose terminal(lift/open-mouthed)above and below
Switch position indicator red-green
Switching toggle(MCB component)in colour designationg the rated current
Busbar positioning optionally above or below
Comprehensive range of accessories suitable for subsequent installation
Electrical technical data
Standards IEC / EN 61009
Tripping time Instantaneous
Type G 10 ms delay
Rated voltage 230V 50Hz
Operational voltage range 196-253V
Rated tripping current 30, 100, 300mA
Rated non-tripping current 0.5In
Sensitivity Type A and type AC
Selectivity class 3
Rated breaking capacity 10kA
Rated current 6-40A
Characteristic B,C
Maximum back-up fuse(short circuit) 100A gl(>10kA)
Endurance electrical life >4000 operating cycles
mechnical life >20000 operating cycles
Combined electronic type RCD/MCD device
High breaking capacity:10KA
Line voltage-independent tripping
Compatible with standard busbar
Twin-purpose terminal(lift/open-mouthed)above and below
Switch position indicator red-green
Switching toggle(MCB component)in colour designationg the rated current
Busbar positioning optionally above or below
Comprehensive range of accessories suitable for subsequent installation
Electrical technical data
Standards IEC / EN 61009
Tripping time Instantaneous
Type G 10 ms delay
Rated voltage 230V 50Hz
Operational voltage range 196-253V
Rated tripping current 30, 100, 300mA
Rated non-tripping current 0.5In
Sensitivity Type A and type AC
Selectivity class 3
Rated breaking capacity 10kA
Rated current 6-40A
Characteristic B,C
Maximum back-up fuse(short circuit) 100A gl(>10kA)
Endurance electrical life >4000 operating cycles
mechnical life >20000 operating cycles