A/C Compressor
Specification of compressors
1. application scope: room air conditioners
2. rated voltage/frequency/phase: 220-240V/50hz/1
3. refrigerant : R22
4. rage of ambient temperature: -5~43?
5. range of evaporating temperature: 45~65?6. working capacity : 22.6CM3/rev
7. rated capacity "3850w(220V)
8. motor input power : 1280w(220V)
9. running current : 5.5A (220V)
10. EER: 3.3 W/W
11. refrigeration oil: 4GSDI
12. amount of oil charge : 410ml
13. net weight: 15.6kg
14. motor: motor type, permanent split capacitorted
15. locked rotor amps: 38a( 220V),
16. running capacitor : 30Mf/450V/AC
17. insulation class: class B
18. winding resistance(M/S): 2.07/4.34OM(@20?)
19. outer compound protector: V260-150-141E OR: MRA13401-9201
20. working conditions: NOMINAL OVERLOAD
evaporating temperature 7.2? 10.0
condensing temperature 54.4? 65.8?
super-coding temperature 8.3? 5?
suction gas temperature 35.0? 18.0?
ambient temperature 35.0? 25.0?
21. specific performance
A. temperature of motor winding: 130? max
B. vibration: 40M/S2 max
C. noise: 55Db(A) max
D. LEAKAGE TESTING PRESSURE: 2.95mpa
E. Mechanical strength pressure: 10.5mpa
F. Insulation resistance: >=30MOM
G. Electric strength : 1500V
H. Residual moisture: 200mg max
I. Residual impurity: 40mg max
22. operating conditions
A. start-up voltage( min) : 58% of rated voltage
B. running voltage range:+/-10% of rated voltage
C. when the compressor has been installed into the refrigerating system, it should remain perpendicular to the leveling floor with max inclination no more than 5?
D. the period of turning down and restarting the compressor should be more than 3 minutes
E. the residual moisture in the refrigerating system(not include the compressor ) should not exceed 60ppm, the residual impurity in the refrigerating system( not include the compressor) should not exceed 20mg
F. the filling amount of refrigerant should not 1250g
G. when the electric container cap is installed, the nut screw